 Maintenance Objects
3-965PRI-CDR/SEC-CDR (PRI-CDR Link) 
3
d. This error indicates that the CDR output device is in an off-line state, for 
example, paper jam or paper out for a printer device. The CDR link is torn 
down. Check the CDR output device and act promptly to put it back to 
on-line state. Enter 
test cdr-link primary|secondary
 command to set up 
the CDR link.
e. Software detects an overflow of CDR records generated in the switch due 
to the heavy trunk traffic and low speed CDR output device. If both 
primary and secondary links are ON, the secondary link is torn down 
temporarily for two minutes to speed up the output process to the primary 
link. No action is necessary for this error type.
System Technician-Demanded Tests: Descriptions 
and Error Codes
Always investigate tests in the order presented in the table below when 
inspecting errors in the system. By clearing error codes associated with the 
Link 
Retry Test
, for example, you may also clear errors generated from other tests in 
the testing sequence.
Link Tear Down Test (#213)
This test is destructive.
This test disconnects the existing link between the system and the external CDR 
output device. If the link has been disconnected already, this test just returns 
PASS. All resources allocated for an CDR link are released after this test.
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence D/ND
1
1. D = Destructive; ND = Nondestructive
Link Tear Down Test (#213) X D
Link Retry Test (#215) X X ND