 Maintenance Objects
3-964PRI-CDR/SEC-CDR (PRI-CDR Link) 
3
Notes:
a. System Technician has busied out the CDR link to out-of-service state. The 
CDR link is torn down.
b. Link Retry Test (#215) fails. The Aux Data field contains either the Channel 
ID of Data Channels on the TN798 Processor circuit pack (that is, 3 for 
Channel 01, 4 for Channel 02, 5 for Channel 03, 6 for Channel 04, and 9 
for EIA port) or an Error Code of 99 indicating that no data channels are 
available for setting up the link, or an Error Type of 255 indicating an 
internal system error. Refer to the preceding ‘‘Procedures for Restoring the 
CDR Link’’ for resolution.
c. The CDR physical link is down due to the following causes: cable to the 
CDR output device is disconnected; CDR output device is powered off, 
the data extension where the CDR output device connects to has been 
busied out or there is a scheduled daily interchange. The Aux Data field 
contains the Channel ID of Data Channels on the TN798 Processor circuit 
pack (that is, 3 for Channel 01, 4 for Channel 02, 5 for Channel 03, 6 for 
Channel 04, and 9 for EIA port). Check the connectivity of wire and cable 
among wall jacket, data module, and the CDR output device. Enter 
status 
data extension
 and verify that the data extension of the CDR output 
device is in the in-service/idle state. If the data extension is not available, 
then refer to the preceding ‘‘Procedures for Restoring the CDR Link’’
 for 
resolution. Issue the 
display system-parameters-maintenance
command to see the start time of daily maintenance. If the error occurs 
and is resolved during the interval of daily maintenance, then the error can 
be ignored.
1025 (d)
1281 (e)
1. The MTP Reset Test (#101) logs you off. The MTP Dual Port Ram Test (#104) can also log you off. 
Manually repeat the command with the ‘‘long’’ option for the designated number of times when 
testing from the PPN SAT.
2. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
3. Minor alarms on this MO may be downgraded to Warning alarms based on the value used in the 
set options command.