■ The 
Result
 should be 
PASS
 for each test number. If the any of the 
tests fail, refer to 
‘‘ATM-BCH (ATM B-Channel Trunk)’’
.
Possible Causes
1. The TN230X board is in a slot different from the DEFINITY administration.
2. The TN230X did not complete board insertion.
Physical Layer
Is there an optical signal between the TN230X and the A500?
1. Does the TN230X’s yellow LED flash 100ms on/100ms off, indicating a loss 
of signal on the fiber? Recall that the TN230X detects continuity problems 
with either the Transmit (bottom) or the Receive (top) fibers.
2. Is the A500 port’s CD LED off, indicating a loss of signal on the fiber? Note 
that the A500 detects continuity problems only with the Receive 
(right-hand) fiber; the state of the Transmit (left-hand) fiber is not detected.
3. Enter 
show signaling summary
 on the A500 console. 
Figure 1-49
 shows 
the screen output.
test board 2a01
 TEST RESULTS
 Port Maintenance Name Alt. Name Test No. Result Error Code
 02A01 ATM-EI 316 PASS 
 02A01 ATM-EI 598 PASS 
 02A01 ATM-EI 1258 PASS 
 02A01 ATM-EI 241 PASS 
 02A01 ATM-EI 304 PASS 
 02A01 ATM-EI 1259 PASS 