Maintenance for csi systems 
1-113ATM Tips 
1
Figure 1-41. Screen output for the show signaling summary command
a. If an A500 port to which a DEFINITY port network is attached is not 
listed in this display, it is likely that the port was administered 
incorrectly as having no UNI signaling (
admin link
 command).
Ensure that fields listed have the values indicated below.
2. If the A500 was administered using hard-coded PNNI routes to identify 
each endpoint, enter 
show signaling routes
 on the A500 console. Figure 
1-42 shows the screen output from the command.
Field Value
IntType Network
If it is User, links will not come up between the PPN and 
the EPN.
Signaling UNI3.1
If it is UNI3.0, links will not come up between the PPN 
and the EPN.
ILMI Preferred value of is No, however this alone does not 
prevent links from coming up between the PPN and an 
EPN.
SAP State May or may not be UP. Their values depend on more than 
just whether the port was marked as UP. (See 
highlighted data for SAP State in 
Figure 1-41.)
A500:show signaling summary
Port loc VCI SAP IntType Signaling ILMI SAP State State
------ ------- --- ------- ----------- ---- ------------ -----
A1.1 1 1 Network UNI3.1 No UP UP
A1.2 2 2 Network UNI3.1 No UP UP