Installation Guide

Installation Instructions
4 | P a g e v 1 . 0 (06 / 2 0 2 2 )
Clearance Information AS/NZS 3000:2018 Wiring Rules - Figure 4.9
IC Rating AS/NZS 60598.2.2: 2016
1. A closed luminaire that allows building insulation to come into contact with its sides and to cover it.
2. Type IC-4 recessed luminaire can be used together with building insulation that can safely be
exposed continuously to temperatures up to 90°C may abut and cover the luminaire;
3. The declared IC-4 rating is based on the default testing ambient temperatures 25°C according to the
standard.
LOCATION
DISTANCE
DESCRIPTION
HCB
0 mm
(Minimum)
Clearance between the top of the recessed luminaire and any structural members,
building elements or objects above it.
SCB
0 mm
(Minimum)
Clearance between the side of the recessed luminaire and any structural members,
building elements or objects.
SCI
0 mm
(Abutted)
Insulation can be abutted against the side of recessed luminaire and covered as per
IC-4 Rating. See IC-4 Rating section for more details.
SCG
100mm
Auxiliary equipment/driver/transformer must be placed 100mm away from the luminaire.
It can be placed under the thermal insulation and covered.
RISK OF FIRE – Required clearance from structural members and building elements
SCB = 0 mm HCB = 0 mm