User's Manual
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Site Wiring Requirements
Drive Module Site Preparation Guide 19
Site Wiring Requirements
Review the following information when preparing the drive module or E2400 command 
module installation site.
•
Earth ground – The unit must be properly grounded, including an earth ground 
conductor on the AC power source.
•
Circuit overloading – Make sure the power circuits and associated circuit breakers in 
the cabinet and building provide sufficient power and overload protection. To prevent 
possible damage to the unit, isolate its power source from large switching loads (such as 
air conditioning motors).
•
Power interruptions – The drive module or E2400 command module will withstand 
the following applied voltage interruptions: 
•
Input transient: 50% of nominal voltage
•
Duration: one half cycle 
•
Minimum frequency: once every 10 seconds
•
Power failures – Once power is restored after a complete power failure, the unit 
automatically performs a power-up recovery sequence without operator intervention.
Site Wiring and Voltages
The drive modules and E2400 command module use wide-ranging, redundant power 
supplies that automatically match voltages to the AC power source. They are a 120/220 
VAC, 50/60 Hz units that meet standard voltage requirements for both domestic (USA) 
and international (outside USA) operation. They use standard industrial wiring with a 
line-to-neutral or line-to-line power connections (Table 10).










