PG 1 LS-60 Operation Guide The LS-60 programmable communicating thermostat operates via a high-quality, easy-to-use touch screen. To program or adjust your LS-60, simply touch your finger firmly to the screen. The screen will automatically light up and you will hear a “beep.” Do not use a sharp or metallic device; it will scratch the screen.
PG Control Screens HOME Screen Before you operate the /6 please get familiar with these basic control screens. All the /6 functions are accessed through these screens: HOME, MENU, PROGRAM and MANUAL. The /6 touch screen technology allows you to select (by touching) an item and change it using the +/- arrows or the time arrows. The HOME screen is displayed when the unit is operating. Touching the HOME icon on another screen will always return you to this screen.
MENU Screen The MENU screen is the gateway to many functions or settings of the /6 . It is displayed when you press the MENU button. [See page 10 for details] Set Time Touch this area to set the time of day. Left arrow goes back, right arrow goes forward. Differential to set for 2nd Stage start. Chirp set Touch this to turn the audible chirp on or off. Filter Timer set Touch and hold 5 sec to change.
PG PROGRAM Screen The stand alone PROGRAM screen sets the /6 control for your home HVAC system with out a central controller. Press and hold PROG for 10 sec to access it. After that it is displayed when you press the PROG button. [See page 8 for details] Return HOME When programming is complete touch this to run your program and return to the HOME screen. Set Time Slot Touch this area to set the Time Slot you want to program.
MANUAL Screen The Manual Screen control screen is where you can make temporary changes to your /6 ’s operation. From the Full HOME screen, touch the main temperature display to use this screen. [See page 13 for details] Room Temperature Target Temperature Manual Override Indicator Shows TEMPORARY when you have modified the Target Temperature Temp Up / Temp Down arrows Touch these to raise and lower the manual override Target Temp.
PG Simple HOME Screen Make this the default HOME screen for your /6 by holding the PROG button for 12 seconds. This Simple HOME screen gives you limited access to the /6 ’s on screen display and no programming capability. It makes the /6 behave like a simple one setting Current Room Thermostat Radio thermostat. The simple screen is useful for people who do not want a complex progam changing their target temperatures each day.
Initial Settings Press MENU to to access the following commands (from HOME screen). Set day of the week Touch the Day of the week area to cycle through the days of the week to select the current day. Set time of day Touch the Time of Day arrows to move the time selection forward or backward until it displays the current time. Touch and hold for faster setting. Backward Forward Set oF-oC display Touch the oF and it will toggle to oC.
PG Auto-Run Program The /6 comes pre-programmed with an EPA approved program. This program is recommended by the EPA for energy efficiency. We strongly recommend that you Auto-Run this program for one week, and see if it works for you. If it does not fit your needs you can always input a custom program. To run the EPA program, set the mode switch to HEAT or COOL. Press the MENU button and use the arrows by the time display to set the time. Touch the DAY area and advance it to select the present day.
PROGRAM cont. Select the day you want to program. The day of the week starts at SU - Sunday and can be advanced to the day you want to program. Touch the day of the week area to cycle through the days of the week to the desired day. Select the time slot (period) you want to program (MORN, DAY, EVEN, NITE). Touch the time slot area to cycle through to the desired period. Select the desired start time of that time slot. Touch the time arrows to select the desired period’s starting time.
PG MENU Screen Functions Press MENU to bring up MENU screen. TIME of DAY Touch the left (down) or right (up) arrows next to the time display to set the current time (1 minute per touch). Touch and hold the arrow for fast time set (15 minute jumps). DAY of Week Touch DAY area to select present day.
F C Set - Touch this to switch the temperature display scale from oF to oC . FILTER - AIR FILTER ALERT - The LS-60 can be programmed to remind you when the HVAC sytem’s air filter needs changing. Touch FILTER. The display will show the usage to date. Touch FILTER for over 3 seconds and the display will change to LIMIT. Touch arrows to set desired usage limit before filter alert comes on home screen. When this limit is reached, FILTER will be on home screen and the CHECK FILTER indicator lights.
PG CALIBRATE Your thermostat was accurately calibrated at the factory to ±1° F of actual ambient temperature. You do have the option, however, to change the display temperature to match that of a previous thermostat, or to match another thermostat already in your home. The range of change is from -6°F to +6°F or -3°C to +3°C. To change your Thermostat Calibration, touch MENU and then touch CALIBRATE. Use the + / - to adjust the displayed temperature up or down, as desired.
MANUAL Screen Functions The LS-60 has 4 manual override commands. The manual screen is accessed by touching the large current temperature display in the middle of the HOME screen. IMPORTANT: The Mode must be in HEAT or COOL to access the manual screen. TEMPORARY override Touch the + / - arrows to select your desired temporary Target Temperature. Touch HOME to return to operation. The TEMPORARY icon will display indicating you have modified the Target Temperature for the current Time Slot only.
PG weekly program. To use it touch HOLIDAY on the temporary screen. The default holiday program is shown below. To modify this program, touch the PROGRAM button and then touch the DAY area until HOLIDAY appears (after SAT). The default HOLIDAY program is set as 2 time slots; all day (same target MORN, DAY and EVEN) and a different target for NITE. [Default program: HEAT 70oF all day and 62oF at night. COOL 78oF all day and 82oF at night.
MODE Button The mode button sets the LS-60 to HEAT COOL or OFF modes. Press it once to step to the next mode. If the LS-60 is in OFF and you want to return to the mode you were previously in, touch the OFF indicator on screen. FAN Button The fan control is normally in AUTO mode, meaning that the fan operates automatically with the HVAC system and the thermostat.
PG Compressor Protection The LS-60 has a minimum cycle time of 4 minutes to protect your compressor in cool and in heat pump (if you have one). The Home screen will show a small clock and A/C during this time and the compressor will not come on until the 4 minute delay is over. Communicating Thermostat The LS-60 has 2 RTM-1 radio ports. These allow your thermostat to communicate with other systems. Using USNAP Radios The USNAP ports allow you to connect your LS-60 to a wireless network.