Service Manual

3 Troubleshooting
44
Service Manual
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Outlet Temp
High
Outlet water temperature has exceeded the
maximum outlet water temperature.
Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the
Knight Wall Mount Installation and Operation Manual
the proper piping methods for the Knight wall mount
boiler.
• Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check wiring back
to the main control board. Replace the main control
board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight Wall Mount
Boiler Installation and Operation Manual for boiler
pump specifications.
Replace the main control board.
Low 24 vac
120 vac input to the main control board has
dropped below 80 vac.
Check 120 vac supply to the transformer.
Check wiring connections at the low voltage
terminal strip.
Check the wire size/length to remote devices.
Replace the transformer.
Fatal Error
The control module has detected parameter
settings that are out of range.
Restore the parameter defaults from the optional PC
software.
Replace the control module.
Memory Error
A lockout occurs at the same time as a
power outage.
Reset control module.