Product Overview
Lochinvar, LLC
300 Maddox Simpson Parkway
Lebanon, Tennessee 37090
P: 615.889.8900 / F: 615.547.1000
Lochinvar.com
DIMENSIONS AND SPECIFICATIONS
ARMOR WATER HEATER
*Canada Only
† AHRI Certified Models
WAN-CA
Website Update 12/2021 -Printed in U.S.A
ARMOR
TM
WALL MOUNT WATER HEATER DIMENSIONS AND SPECIFICATIONS
Model Btu/hr GPH @ Gas Water Air Vent Shipping
Number Input 100° Rise A B C D E F G H I Conn. Conn. Inlet Size Wt. (lbs.)
WAN125PM* 125,000 145 29-1/4” 18” 13” 7” 13” 3-1/2” 2-3/4” 5-1/2” 6” 1/2” 1” 3” 3” 145
WAN200PM* 199,000 232 29-1/4” 25” 20” 14” 11-3/4” 3-1/2” 1-1/2” 5-1/2” 13” 1/2” 1-1/4” 3” 3” 177
WAN201PM† 201,000 232 29-1/4” 25” 20” 14” 11-3/4” 3-1/2” 1-1/2” 5-1/2” 13” 1/2” 1-1/4” 3” 3” 177
> High Voltage Terminal Strip
120 VAC / 60 Hertz / 1 Phase Power Supply
Pump Control Contacts
Water Heater Pump Control Contacts
Building Recirculation Pump Control Contacts
> Low Voltage Terminal Strip
24 VAC Louver Relay
Louver Proving Switch Contacts
Flow Switch Contacts
Alarm Contacts
Runtime Contacts
Tank Sensor Contacts
Cascade Contacts
0-10 VDC BMS External Control Contacts
0-10 VDC Boiler Rate Output Contacts
STANDARD FEATURES
>
†
AHRI Certified 96% Thermal Efficiency
> Wall Mounted Models
> Modulating Burner with 5:1 Turndown
Direct-Spark Ignition
Low NOx Operation
Sealed Combustion
Low Gas Pressure Operation
> Vertical & Horizontal Direct-Vent
PVC/CPVC, Polypropylene or SS up to 100 Feet
PVC/CPVC, Polypropylene Sidewall
Vent Termination
> Stainless Steel Heat Exchanger
All Welded Construction, Gasketless Design
160 psi Working Pressure
Natural to L.P. Conversion Kit
Stainless Steel Circulating Pump
Flow Switch
Temperature & Pressure Relief Valve
Tank Sensor
Adjustable High Limit w/ Manual Reset
Automatic Reset High Limit
Condensate Trap
Zero Clearances to Combustible Material
5 Year Limited Warranty (See Warranty for Details)
1 Year Parts Warranty (See Warranty for Details)
SMART SYSTEM
TM
FEATURES
> SMART SYSTEM
TM
Digital Operating Control
> Multi Color Graphic LCD Display
> Built in Cascading Sequencer for up to 8 Water Heaters
Multiple Size Water Heater Cascade
Lead Lag
Efficiency Optimization
> Building Management System Integration
Modbus Communication (Optional)
0-10 VDC Input to Control Modulation or Set point
0-10 VDC Modulation Rate Output
0-10 VDC Input to Enable/Disable call for heat
Access to BMS Settings Through Graphic LCD Display
Low Water Flow Safety Control & Indication
Inlet & Outlet Temperature Sensors & Readout
Flue Temperature Sensor
Water Heater Pump Control
Pump Delay with Freeze Protection
Pump Exercise
Night Setback
Building Recirculation Loop Pump Control
Time Clock
> Maintenance Reminder
Ability to program installer name and number into the
product as service contact
OPTIONAL EQUIPMENT
Audible Alarm
Condensate Neutralization Kit
Concentric Vent Kit (3” PVC/CPVC only)
Modbus or BACnet MSTP Communications
BMS Gateway to LonWorks or BACnet IP
SMART SYSTEM PC Software
FIRING CONTROL SYSTEMS
M9 Standard Construction
7-1/2"
H
16"
I
C
E
F
G
2-3/4"
15-1/2"
D
B
1-3/4"
A
TOPSIDEBOTTOM
RELIEF
VALVE
AIR
INTAKE
FLUE
ELECTRICAL
CONNECTIONS
GAS
CONDENSATE
TRAP
CONDENSATE
LINE
WATER
INLET
WATER
OUTLET
8"
18-1/2"
7-1/2"
H
16"
I
C
E
F
G
2-3/4"
15-1/2"
D
B
1-3/4"
A
TOPSIDEBOTTOM
RELIEF
VALVE
AIR
INTAKE
FLUE
ELECTRICAL
CONNECTIONS
GAS
CONDENSATE
TRAP
CONDENSATE
LINE
WATER
INLET
WATER
OUTLET
8"
18-1/2"
7-1/2"
H
16"
I
C
E
F
G
2-3/4"
15-1/2"
D
B
1-3/4"
A
TOPSIDEBOTTOM
RELIEF
VALVE
AIR
INTAKE
FLUE
ELECTRICAL
CONNECTIONS
GAS
CONDENSATE
TRAP
CONDENSATE
LINE
WATER
INLET
WATER
OUTLET
8"
18-1/2"
Model Number Guide
WA N 125 PM
Model
Pump Mount
Natural Gas
Btu/hr Input
Wall Mount Armor Water Heater,
Natural Gas,
125,000 Btu/hr Input,
Pump Mount