SYNC-I-O Rev N Installation & Operation Manual Models: 1.0 - 1.3 - 1.5 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the SYNC Service Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage. Save this manual for future reference.
Contents HAZARD DEFINITIONS .................................................... 2 PLEASE READ BEFORE PROCEEDING ........................ 3 THE SYNC -- HOW IT WORKS...................................... 4-5 RATINGS ........................................................................... 6 1. DETERMINE BOILER LOCATION Closet and Alcove Installations .......................................... 7 Provide Air Openings to Room .......................................... 9 Flooring and Foundation ...............
Installation & Operation Manual Please read before proceeding WARNING Installer – Read all instructions, including this manual and the SYNC Service Manual, before installing. Perform steps in the order given. User – This manual is for use only by a qualified heating installer/ service technician. Refer to the User’s Information Manual for your reference. NOTICE • To avoid electric shock, disconnect electrical supply before performing maintenance.
Installation & Operation Manual The SYNC - How it works... 1. Access cover - front Provides access to the gas train and the heat exchanger. 2. Air intake adapter Allows for the connection of the PVC air intake pipe to the boiler. 3. Air pressure switches The air pressure switches detect blocked flue/vent conditions. 4. Air shrouds (1.0 Model only) The air shrouds control air and gas flow into the burners. 5. Automatic air vents Designed to remove trapped air from the heat exchanger coils. 6.
Installation & Operation Manual The SYNC - How it works... (continued) Models 1.0 - 1.3 - 1.5 12 40 42 30 2 34 3 17 31 13 27 28 18 19 16 21 44 1 38 35 11 Front View Rear View 4 1.
Installation & Operation Manual Ratings SYNC AHRI Rating Net Input Model Number Gross Output MBH MBH Note: Change “N” to “L” for L.P. gas models. Other Specifications (Note 4) (Note 1) AHRI Ratings Water, MBH Vent Size Appliance Water Content Gallons Outlet Water 8.4 3" (2) - 2" 1½" 6" 6" Inlet Water Gas Connections Air Size (Note 3) (Note 2) Min Max SBN1000 100 1000 941 818 SBN1300 130 1300 1237 1076 10.0 3" (2) - 2" 1½" 6" 6" SBN1500 150 1500 1444 1256 11.
Installation & Operation Manual 1 Determine boiler location Installation must comply with: WARNING This appliance is certified as an indoor appliance. Do not install the appliance outdoors or locate where the appliance will be exposed to freezing temperatures or to temperatures that exceed 100°F. Do not install the appliance where the relative humidity may exceed 93%.
Installation & Operation Manual 1 Determine boiler location Figure 1-1 Closet Installation - Minimum Required Clearances 1/4” (6 MM) MINIMUM CLEARANCE AROUND HOT WATER PIPES 1” (25 MM) MINIMUM CLEARANCE AROUND VENT PIPES WARNING For closet installations, CPVC, polypropylene or stainless steel vent material MUST BE used in a closet structure due to elevated temperatures. Failure to follow this warning could result in fire, personal injury, or death.
Installation & Operation Manual 1 Determine boiler location (continued) Provide air openings to room: Vent and air piping The SYNC alone in boiler room The SYNC requires a special vent system, designed for pressurized venting. 1. No air ventilation openings into the boiler room are needed when clearances around the SYNC are at least equal to the SERVICE clearances shown in FIG.’s 1-1 and 1-2. For spaces that do NOT supply this clearance, provide two openings as shown in FIG. 1-1.
Installation & Operation Manual 1 Determine boiler location Table 1A Corrosive Contaminants and Sources Products to avoid: Spray cans containing chloro/fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergen
Installation & Operation Manual 1 Determine boiler location When removing a boiler from existing common vent system: DANGER WARNING Do not install the SYNC into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death, or substantial property damage. Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Installation & Operation Manual 1 Determine boiler location Combustion and ventilation air requirements for appliances drawing air from the equipment room Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
Installation & Operation Manual 1 Determine boiler location (continued) Where two openings are provided, one must be within 12" (30cm) of the ceiling and one must be within 12" (30cm) of the floor of the equipment room. Each opening must have net free area as specified in the chart below (Table 1B). Single openings shall commence within 12" (30cm) of the ceiling. Under no circumstances should the CAUTION equipment room ever be under negative pressure.
Installation & Operation Manual 2 General venting Direct venting options - Sidewall Vent Figure 2-1 Two Pipe Sidewall Termination See page 22 for more details Direct venting options - Vertical Vent Figure 2- 2 Two Pipe Vertical Termination See page 26 for more details 14 Figure 2-3 Vertical Vent, Sidewall Air - See page 18 for more details
Installation & Operation Manual 2 General venting (continued) Install vent and combustion air piping DANGER The SYNC boiler must be vented and supplied with combustion and ventilation air as described in this section. Ensure the vent and air piping and the combustion air supply comply with these instructions regarding vent system, air system, and combustion air quality. See also Section 1 of this manual.
Installation & Operation Manual 2 General venting Sizing Requirements for installation in Canada 1. 2. 3. The SYNC boiler uses model specific combustion air intake and vent piping sizes as detailed in Table 2A below. Installations must be made with a vent pipe system certified to ULC-S636. The first three (3) feet of plastic vent pipe from the appliance flue outlet must be readily accessible for visual inspection.
Installation & Operation Manual 2 General venting (continued) Materials Air inlet pipe materials: The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list: PVC, CPVC, Polypropylene or ABS Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet) Galvanized steel vent pipe with joints and seams sealed as specified in this section. Type “B” double-wall vent with joints and seams sealed as specified in this section.
Installation & Operation Manual 2 General venting Optional room air Applications utilizing the SYNC boiler may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room. In order to use the room air venting option the following conditions and considerations must be followed. • • • • • The unit MUST be installed with the appropriate room air inlet cover (factory installed).
Installation & Operation Manual 2 General venting (continued) PVC/CPVC 1. This product has been approved for use with the PVC/CPVC vent materials listed in Table 2C. Installing vent and air piping WARNING The vent connection to the appliance must be made with the starter CPVC pipe section provided with the appliance if PVC/CPVC vent is to be used. The field provided vent fittings must be cemented to the CPVC pipe section using an “All Purpose Cement” suitable for PVC and CPVC pipe.
Installation & Operation Manual 2 General venting Polypropylene WARNING This product has been approved for use with polypropylene vent with the manufacturers listed in Table 2D. All terminations must comply with listed options in this manual and be a single-wall vent offering. For use of flex pipe, it is recommended to have the vent material in 32°F or higher ambient space before bending at installation.
Installation & Operation Manual 2 General venting (continued) Stainless steel vent Installation of a stainless steel vent system should adhere to the stainless steel vent manufacturer’s installation instructions supplied with the vent system. NOTICE This product has been approved for use with stainless steel using only FasNSeal vent systems. WARNING NOTICE NOTICE Use only the materials, vent systems, and terminations listed in Table 2F.
Installation & Operation Manual 3 Sidewall direct venting Vent/air termination – sidewall WARNING WARNING Follow instructions below when determining vent location to avoid possibility of severe personal injury, death, or substantial property damage. A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks.
Installation & Operation Manual 3 Sidewall direct venting (continued) Vent/air termination – sidewall Figure 3-2A Clearance to Gravity Air Inlets Figure 3-1C Alternate Stainless Steel Sidewall Termination w/Field Supplied Fittings NOTICE PVC/CPVC or ABS is acceptable air inlet pipe material. 12" MIN. TO BOILER INTAKE AIR CONNECTION VENT / AIR TERMINATION 12" MIN. 12" (305 MM) MIN 15" (381 MM) MAX FROM BOILER VENT PIPE CONNECTION 12" (305 MM) MIN 12" MIN.
Installation & Operation Manual 3 Sidewall direct venting Figure 3-3B Alternate Clearance to Forced Air Inlets w/ Field Supplied Fittings IF LESS THAN 10’ (3 M) 36” (914 MM) MIN 8. PVC/CPVC terminations are designed to accommodate any wall thickness of standard constructions per the directions found in this manual. 9. Stainless steel terminations are designed to penetrate walls with a thickness up to 9.25 inches of standard construction.
Installation & Operation Manual 3 Sidewall direct venting (continued) Prepare wall penetrations (Alternate Field Supplied Options) 1. Air pipe penetration (see FIG. 3-4B): a. Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter. 2. Vent pipe penetration (see FIG. 3-4B): a. Cut a hole for the vent pipe.
Installation & Operation Manual 4 Vertical direct venting Vent/air termination – vertical WARNING Follow instructions below when determining vent location to avoid possibility of severe personal injury, death or substantial property damage.
Installation & Operation Manual 4 Vertical direct venting (continued) Multiple vent/air terminations Figure 4-3 Vertical Terminations with Multiple Boilers 1. When terminating multiple SYNC boilers, terminate each vent/air connection as described in this manual (FIG. 4-3). WARNING Terminate all vent pipes at the same height and all air pipes at the same height to avoid recirculation of flue products and the possibility of severe personal injury, death, or substantial property damage. 2.
Installation & Operation Manual 5 Hydronic piping System water piping methods General piping information The SYNC is designed to function in a closed loop pressurized system not less than 12 psi (83 kPa). A temperature and pressure gauge is included to monitor system pressure and outlet temperature and should be located on the boiler outlet. Basic steps are listed below along with illustrations on the following pages (FIG.
Installation & Operation Manual 5 Hydronic piping (continued) Circulator sizing The SYNC heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graph in FIG. 5-4 for pressure drop through the SYNC heat exchanger. Near boiler piping connections Figure 5-1A Near Boiler Piping w/Y-Strainer DRAIN (TYPICAL) SYSTEM SUPPLY SENSOR (NOTICE: A SYSTEM SUPPLY SENSOR MUST BE INSTALLED FOR PROPER BOILER OPERATION.
Installation & Operation Manual 5 Hydronic piping Hot Water Generator pump sizing The SYNC has two (2) heat exchangers that require two (2) individual pumps for proper installation in the boiler loop and an additional two (2) pumps for the Hot Water Generator loop. Hot Water Pump Head Loss = Ft. of Head for Heat Exchanger 1 (at required flow) + Ft.
Installation & Operation Manual 5 Hydronic piping (continued) Figure 5-4 Pressure Drop vs.
Installation & Operation Manual 5 Hydronic piping Figure 5-5 Single Boiler - Primary/Secondary Piping NOTICE FR OM A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
Installation & Operation Manual 5 Hydronic piping (continued) Figure 5-6 Multiple Boilers - Primary/Secondary Piping Number of Units 3 4 5 6 7 Manifold Pipe Sizes in Inches (mm) Model 2 1000 1300 1500 4 (102) 5 (127) 5 (127) 5 (127) 5 (127) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 8 (203) 8 (203) NOTICE FR OM SY ST 8 (203) 8 (203) 8 (203) 8 8 (203) 8 (203) 8 (203) 8 (203) 8 (203) 10 (254) A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
Installation & Operation Manual 6 Gas connections Connecting gas supply piping 1. Refer to FIG. 6-1 to pipe gas to the boiler. a. Install ground joint union for servicing, when required. b. In Canada – When using manual main shutoff valves, it must be identified by the installer. 2. Install sediment trap / drip leg. Figure 6-1 Gas Supply Piping WARNING GAS SUPPLY Ensure that the high gas pressure regulator is at least 10 feet (3 m) upstream of the appliance. 3.
Installation & Operation Manual 6 Gas connections WARNING (continued) Use two wrenches when tightening gas piping at boiler (FIG. 6-2), using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components. Figure 6-2 Inlet Pipe with Backup Wrench Natural gas supply pressure requirements 1. Pressure required at the gas valve inlet pressure port: • Maximum 14 inches w.c. (3.
Installation & Operation Manual 6 Gas connections Table 6A Natural Gas Pipe Size Chart TABLE - 6A GAS PIPING SIZE CHART Nominal Iron Pipe Size Inches 10 20 1½ 2,150 1,500 2 4,100 2½ Length of Pipe in Straight Feet 30 40 50 60 70 80 90 100 125 150 175 1,210 1,020 923 830 769 707 666 636 564 513 472 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 3 11,200 7,900 6,
Installation & Operation Manual 6 Gas connections (continued) Do not check for gas leaks with an open WARNING flame -- use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage. 14. Turn on the gas supply at the manual gas valve. 15. Turn the power switch to the “ON” position. 16.
Installation & Operation Manual 7 Field wiring WARNING NOTICE Installation must comply with: ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death. 1. National Electrical Code and any other national, state, provincial, or local codes, or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.
Installation & Operation Manual 7 Field wiring (continued) Low voltage connections 1. Route all low voltage wires through the knockouts in the rear of the boiler, as shown in FIG. 7-2. 2. Connect low voltage wiring to low voltage connection board as shown in FIG. 7-3 on page 41 of this manual and the boiler wiring diagram. Figure 7-2 Routing Field Wiring LOW VOLTAGE WIRING KNOCKOUTS LOW VOLTAGE CONNECTION BOARD Hot Water thermostat Generator (HW) 1.
Installation & Operation Manual 7 Field wiring System supply sensor Wiring of the cascade 1. By installing the system supply sensor into the supply of the primary loop, the temperature of the system supply can be controlled. The SMART TOUCH control automatically detects the presence of this sensor, and controls the boiler firing rate to maintain the system supply temperature to the set point. When wiring the boilers for Cascade operation, select one boiler as the Leader boiler.
TANK SENSOR A B A B TO NEXT BOILER SHIELD SHIELD MODBUS COMMUNICATION BUS TO NEXT BOILER 23 OUT DOOR 24 SENSOR 25 TANK 26 SENSOR 27 SHIELD GND 28 B 29 A 30 SHIELD GND 21 SYSTEM 22 SENSOR 15 SHIELD GND 16 A 17 B 18 SHIELD GND 19 (+) 0 - 10V INPUT 20 (-) LBL20052 REV B 10 FLOW SWITCH 11 TANK 12 THERMOSTAT 13 R ENABLE 14 W 9 HEX 1 8 FLOW SWITCH CASCADE FROM PREVIOUS BOILER SHIELD A B ALARM CONTACTS RUN TIME CONTACTS LOUVER PROVING 7 HEX 2 1 2 3 4 5 6 MOD BUS OUTDOOR SENSOR SYSTEM SENSOR
Installation & Operation Manual 8 Condensate disposal Condensate drain NOTICE 1. This boiler is a high efficiency appliance that produces condensate. 2. The rear of the boiler has a 1/2 inch (12.7 mm) PVC union for connection of a 1/2 inch (12.7 mm) PVC pipe (FIG. 8-1). 3. Slope condensate tubing down and away from the boiler into a drain or condensate neutralizing filter. Condensate from the SYNC will be slightly acidic (typically with a pH from 3 to 5).
Installation & Operation Manual 9 Start-up Check/control water chemistry CAUTION Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and gaskets in the system could occur, resulting in substantial property damage. Hardness less than 7 grains 1. Consult local water treatment companies for hard water areas (above 7 grains hardness). 4. At initial fill and during boiler startup and testing, check system thoroughly for any leaks.
Installation & Operation Manual 9 Start-up Check for gas leaks WARNING Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the top access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once. DO NOT adjust or attempt to measure WARNING gas valve outlet pressure.
Installation & Operation Manual 9 Start-up (continued) Final checks before starting the boiler Check vent piping and air piping Read the SYNC Service Manual to familiarize yourself with SMART TOUCH control module operation. Read this manual, page 46 for proper steps to start boiler. 1. Check for gastight seal at every connection, seam of air piping, and vent piping. Verify the boiler and system are full of water and all system components are correctly set for operation.
Installation & Operation Manual 9 Start-up Figure 9-2 Operating Instructions FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas.
Installation & Operation Manual 9 Start-up (continued) Check flame and combustion (continued) Set space heating operation 4. Navigate to the Service Mode Screen from the Status Screen by pressing the MAIN button and then the SERVICE MODE button. Verify space heat circulator mode 5.
Installation & Operation Manual 9 Start-up 6. If no other changes are necessary, press the BACK button to return to the Parameter List Screen. 7. Once all the necessary adjustments have been made, press the BACK button to return to the Setup Screen. 8. Press the SAVE button to program all changes made to the set points and return to the Status Screen.
Installation & Operation Manual 10 Operating information General How the boiler operates The SYNC uses advanced stainless steel heat exchangers and electronic control modules that allow fully condensing operation. The blowers pull in air and push flue products out of the boiler through the heat exchangers and flue piping. The control modules regulate blower speed to control the boiler firing rate.
Installation & Operation Manual 10 Operating information Gradient limiting Protection features If during operation of the boiler the outlet water temperature is rising too quickly, the control will reduce the firing rate to its lowest setting. Outlet temperature, flue temperature, and temperature rise limiting Outdoor air reset If an outdoor air sensor is connected, the control module will calculate the set point based on the programmed reset curve.
Installation & Operation Manual 10 Operating information (continued) Monitor external limits High limit operations Connections are provided on the connection board for external limits such as flow switch and a louver proving switch. The SMART TOUCH control will shut off the burner and inhibit relighting whenever any of these external limits open. When outlet temperature exceeds 200°F (93.3°C), high limit action occurs. The boiler shuts down until the outlet water cools down.
Installation & Operation Manual 10 Operating information If the water temperature at the system supply sensor is less than the set point + the turn-off offset - the off-on differential, then the control will initiate a call for heat on the Cascade (see the SYNC Service Manual for an explanation of the offset and differential). The Leader will energize the lead boiler on the Cascade. For a new startup this will be the Leader boiler.
Installation & Operation Manual 10 Operating information (continued) Sequence of operation Note: This unit is equipped with two (2) independent, but synchronized combustion systems. The Heat Exchanger 1 combustion system will fire first. If the demand cannot be met by one (1) combustion system the same sequence of operation will be followed to bring the Heat Exchanger 2 combustion system online. 1.
Installation & Operation Manual 10 Operating information SYNC control module The Status Screen displays boiler status, Cascade addresses, outlet water temperature, inlet water temperature, system temperature, and tank temperature. The boiler can be changed by pressing the ON/OFF button. The Details Screen and Main Menu Screen can be accessed by pressing the appropriate button.
Installation & Operation Manual 10 Operating information (continued) Boiler Configuration - This line shows the current configuration of the two control modules inside the unit. Hot Water Tank Temperature - This is the temperature as measured by the tank sensor in the hot water storage tank. Outlet Water Temperature - This is a calculated temperature based on the readings of the outlet temperatures of the two (2) heat exchangers.
Installation & Operation Manual 10 Operating information Use the Main Menu Screen (FIG. 10-2) to access the screens necessary to set temperatures, operating conditions, and monitor boiler operation. The SYNC is equipped with a SMART TOUCH control system. All menu options are accessed by touching the screen with your finger or a stylus from a PDA.
Installation & Operation Manual 11 Maintenance Maintenance and annual startup Table 11A Service and Maintenance Schedules Service technician (see the following pages for instructions) Owner maintenance (see the SYNC User’s Information Manual for instructions) General: • Address reported problems, if any • Inspect interior; clean and vacuum if necessary; • Check boiler area Daily • Clean condensate trap and fill with fresh water • Check pressure/temperature gauge • Check for leaks (water, gas, fl
Installation & Operation Manual 11 Maintenance WARNING Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
Installation & Operation Manual 11 Maintenance (continued) Flue vent system and air piping 1. Visually inspect the entire flue gas venting system and air piping for blockage, deterioration or leakage. Repair any joints that show signs of leakage. Verify that air inlet pipe is connected and properly sealed. 2. Verify that boiler vent discharge and air intake are clean and free of obstructions.
Installation & Operation Manual 11 Maintenance Inspect ignition sense electrodes and flame 1. Remove the ignition and flame sense electrodes from the boiler heat exchanger access covers. 2. Remove any deposits accumulated on the ignition/ flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones. 3. Replace ignition/flame sense electrodes, making sure the gaskets are in good condition and correctly positioned. Check burner flame 1.
Installation & Operation Manual 11 Maintenance (continued) Cleaning boiler heat exchanger For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 11B - Heat Exchanger Cleaning Kits. 1. Shut down boiler: • Follow the “To Turn Off Gas to Appliance” instructions for the boiler in Section 9 - Startup. • Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain. 2.
Installation & Operation Manual 11 Maintenance Handling ceramic fiber materials REMOVAL OF COMBUSTION CHAMBER LINING WARNING The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).
Installation & Operation Manual 12 Diagrams Figure 12-1 Ladder Diagram_Part 1 BOX DEPICTS OPTIONAL ITEMS LOW VOLTAGE 120 VAC HIGH VOLTAGE CONTROL MODULE 1 CONTROL MODULE 2 LOUVER RELAY 1 X8 X6-8 X5-7 X8 X5-7 24V FLAP VALVE 24V LOUVER RELAY 2 X5-4 X5-4 AIR PRESSURE SWITCH X5-14 FLAP VALVE HI-LIMIT AIR PRESSURE SWITCH X5-14 HI-LIMIT X6-8 X5-8 INLET SENSOR INLET SENSOR X5-8 X5-1 OUTLET SENSOR X5-1 OUTLET SENSOR X5-9 X5-9 X5-2 X5-2 FLUE SENSOR FLUE SENSOR X5-3 X5-3 BLOCKED DRAIN
Installation & Operation Manual 12 Diagrams Figure 12-2 Ladder Diagram_Part 2 BOX DEPICTS OPTIONAL ITEMS JUNCTION BOX 120VAC NEUTRAL TERMINAL STRIP 120V SUPPLY "L" LOW VOLTAGE 120 VAC HIGH VOLTAGE GROUND TERMINAL STRIP 120V SUPPLY "N" L1 JUNCTION BOX N LOUVER MOTOR CONTROL MODULE 1 ON / OFF SWITCH F5 X1-6 X1-2 SYSTEM PUMP RELAY X1-4 HEX 1 BOILER PUMP RELAY LOUVER CONTACTS SYSTEM PUMP RELAY 5A HEX 1 BOILER PUMP CONTACTS BOILER PUMP HEX 2 BOILER PUMP CONTACTS BOILER PUMP SYSTEM PUM
Installation & Operation Manual 12 Diagrams (continued) Figure 12-3 Wiring Diagram LOW VOLTAGE 120 VAC HIGH VOLTAGE X3 CM 1 PC INTERFACE BOX DEPICTS OPTIONAL ITEMS X5 PC INTERFACE RELAY BOARD X8 X1-4 OR K1 X1-2 PR BR K2 CN4 CN3-15 BOILER 2 OR CM 2 PC INTERFACE CN3 CN3-16 CASCADE RS485 LOUVER BR CONNECTION BOARD SHIELD JUNCTION BOX LOUVER CONTACTS R2 R1 CONTROL MODULE 1 BOILER 1 BR X4 CN3-14 PR K3 X1-3 SYSTEM PUMP PR CN3-13 SHIELD GY CN3-12 TANK SENSOR CN3-11 HW PUMP R
Notes 66
Notes 67
Revision Notes: Revision A (ECO #C02428) initial release. Revision B (ECO #C03046) reflects the addition of FIG. 5-3 on page 27, the addition of a pressure gauge to FIG. 5-6 on page 30, edits made to FIG. 7-1 on page 35, edits made to the Low Water Cutoff Protection section on page 48 along with the addition of the Flow Sensing Device section. Revision C (ECO #C03223) reflects edits made to the high altitude section on page 6.