Install Instructions

SDT/SET Installation & Operation Manual
0.00
5.00
10.00
15.00
20.00
25.00
0 5 10 15 20 25 30 35
FT/HD
GPM
SDT
/SET065 - 080
FRICTION
LOSS
SOLAR
COIL
BOILER
COIL
Table 3A
Pressure Drop Chart SDT/SET065-080
Table 3C
Pressure Drop Values
MODEL
COIL
CONN.
(IN)
COIL
LENGTH
(FT)
SQ FT
SURFACE
AREA
PRESSURE DROP
SOLAR COIL
(FT / HD)
COIL
LENGTH
(FT)
SQ FT
SURFACE
AREA
PRESSURE DROP
BOILER COIL
(FT / HD)
5
GPM
8
GPM
12
GPM
16
GPM
20
GPM
25
GPM
30
GPM
5
GPM
8
GPM
12
GPM
16
GPM
20
GPM
25
GPM
30
GPM
SDT065 1 41.5 13.5 0.94 2.14 4.35 7.2 10.64 15.72 21.63 28 9.2 0.52 1.18 2.4 3.97 5.86 8.66 11.92
SDT080 1 41.5 13.5 0.94 2.14 4.35 7.2 10.64 15.72 21.63 28 9.2 0.52 1.18 2.4 3.97 5.86 8.66 11.92
SDT119 1 67.3 22 1.38 3.15 6.41 10.6 15.66 23.14 31.84 48.5 16 1.05 2.38 4.84 8.01 11.83 17.48 24.05
SET065 1 41.5 13.5 0.94 2.14 4.35 7.2 10.64 15.72 21.63
SET080 1 41.5 13.5 0.94 2.14 4.35 7.2 10.64 15.72 21.63
SET119 1 67.3 22 1.38 3.15 6.41 10.6 15.66 23.14 31.84
3 Boiler Side Piping (SDT models)
Table 3A Pressure Drop Chart SDT/SET065-080
Table 3C Pressure Drop Values SDT/SET065-119
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
0510152025
FT/HD
GPM
SDT / SET119 FRICTION LOSS
SOLAR
COIL
BOILER
COIL
Table 3B
Pressure Drop Chart SDT/SET119
Table 3B Pressure Drop Chart SDT/SET119
8