13 Troubleshooting (continued)
Table 13-3 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
O˞˝˕ˎ˝ Sˎ˗˜˘˛
Fˊ˞˕˝
(will require a manual
reset once the condition
has been corrected.
Press the RESET
button on the display to
reset.)
One or both of the outlet sensors has
opened or shorted.
Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
Measure the resistances of the sensors and compare
the resistances to the tables on page 83. Replace if
necessary.
I˗˕ˎ˝ Sˎ˗˜˘˛
Fˊ˞˕˝
(will require a manual
reset once the condition
has been corrected.
Press the RESET
button on the display to
reset.)
The inlet sensor is open.
Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
Sˎ˝ P˘˒˗˝ Mˎ˝
The temperature has reached the set point
+ 10°F.
• None
A˗˝˒-Cˢˌ˕˒˗ː
The main control board has received a call
for heat too quickly after the previous call for
heat has ended.
The control board will release the call for heat after 60
seconds.
The control board will release the call for heat if the
outlet temperature drops 10°F.
Dˎ˕˝ˊ T H˒ːˑ
The temperature rise across the heat
exchanger has exceeded the set parameters
for the boiler.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping
for the proper piping methods for the Lochinvar Combi
Boiler.
Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.
If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
Verify that the boiler pump is set to the proper speed
or that the pump is the proper size. Reference
Section 6 - Hydronic Piping for boiler
pump specifications.
The fan speed is being limited due to the
temperature rise across the heat exchanger
exceeding 55°F.
Installation & Service Manual