Install Instructions

93
Combustion Analysis Procedure
1. Turn the main power off to the boiler.
2. Hold the plus the button for five (5) seconds to
enter Service Mode.
3. Once the boiler has modulated up to full fire, measure the
combustion. Place the analyzer probe in the fitting on
the flue adapter. The values should be in the range listed
in Table 13-4. The CO levels should be less than 150 ppm
for a properly installed unit.
If the combustion is not within the specified range,
reference Table 13-5 for possible causes and corrective
actions.
Table 13-5 Troubleshooting Chart - Combustion Levels
POSSIBLE CAUSE CORRECTIVE ACTION
Vent/Air Intake Length
or Obstruction
Refer to Section 3 - General Venting for the proper venting and air intake methods for the
Noble Fire Tube.
Check for obstructions at the vent/air intake terminals.
Gas Supply Pressure
Refer to Section 7 - Gas Connections for the proper gas supply for the Lochinvar Fire Tube.
Dirty/Damaged Burner
Refer to page 79 of this manual for burner removal.
Replace burner if necessary.
Gas Valve Adjustment
Refer to this page of the manual for the gas valve adjustment procedure.
13 Troubleshooting (continued)
Table 13-4 Flue Products
You must replace the cap on the vent
adapter to prevent flue gas spillage into the
room. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
WARNING
Gas valve adjustment procedure
4. Once the combustion analysis is complete, test the safety
shutoff device by turning the manual shutoff switch to
the OFF position and ensuring that the boiler shuts
down and registers an alarm. Turn the manual gas valve
to the ON position and reset the control.
5. Turn the main power off to the boiler and replace the cap
on the sample port.
6. Place the boiler back into normal operation.
If adjustment of the gas valve is deemed necessary, use the
following procedure:
CAUTION
Under normal operating conditions this
valve should not need adjusting.
Locate the throttle adjustment screw on the top of the gas
valve, see FIG.'s 13-2 and 13-3 on page 94. Using a 2.5 mm
Allen wrench, turn the screw 1/8 turn counterclockwise
to increase CO
2
levels or 1/8 turn clockwise to decrease
CO
2
levels. After one adjustment on the valve, follow the
Combustion Analysis to measure the combustion.
If combustion is still not within the specified range,
repeat the procedure. This procedure SHOULD NOT
be performed more than four (4) times. If after four (4)
adjustments and the combustion is still not within the
specified range, revisit the possible causes in Table 13-5
(this page) or replace the gas valve.
Installation & Service Manual
Goal
Natural Gas Propane
CO
2
O
2
CO
2
O
2
Range 8.5% - 10.5% 2.3% - 5.7% 10.0% - 11% 4.1% - 5.6%
Target 9.0% 4.9% 10.5% 4.9%
FIRE TUBE