6 Outdoor installations
Installation & Operation Manual
Outdoor venting
• In order to properly install the appliance in an outdoor
con guration, the appropriate outdoor ready model (ex.
KBX0400N-O) must be purchased WITH a factory
supplied outdoor installation kit.
• In order to properly install the appliance in an outdoor
con guration the optional outdoor kit must be used (see
Table 6A).
• Vent materials for outdoor venting are to be eld supplied.
• Vent materials must be stainless steel.
• e vent must terminate at least 36 inches above the top of
the unit.
• All vent materials must be supported as recommended by
the vent manufacturer.
• e terminations in Table 6B must be used.
Model Indoor to Outdoor Conversion Kit
400 - 1000 100331712
Table 6A Indoor to Outdoor Conversion Kit
Before installing a venting system, follow
all requirements found in the General
Venting section of this manual.
Outdoor vent / air inlet location
Keep venting areas free of obstructions. Keep area clean and free
of combustible and ammable materials. Maintain minimum
clearances to combustibles as stated in this manual.
NOTICE
Only use the vent caps speci ed in this
manual. Personal injury or product
damage may result if any other cap is used,
or if an indoor model is used outdoors.
Properly install all covers, doors, and jacket
panels to ensure proper operation and
prevent a hazardous condition.
Units are self-venting and can be used outdoors when installed
with the optional outdoor kit. All vent materials must be eld
supplied and supported per the vent manufacturer’s instructions.
Combustion air supply must be free of contaminants (see the
Combustion and Ventilation Air Requirements section of this
manual). To prevent recirculation of the ue products into the
combustion air inlet, follow all instructions in this section.
⚠WARNING
Model
DuraVent Z-Flex Heat Fab Metal Fab Security Chimney
Adapter Rain Cap Adapter Rain Cap Adapter Rain Cap Adapter Rain Cap Adapter Rain Cap
400 - 500
FSA-4PVC-4FNS FSRC4 2SVSLA04 2SVSXITC04 9401PVC CCA04EX06 4CGPVCA 4FCSEC-C60 SS4PVCU SS4ECU
650 - 1000
810005231 FSRC6 - - 9601PVC CCA06EX08 6CGPVCA 6FCSEC-C60 SS6PVCU SS6ECU
Table 6B Approved Stainless Steel Adapters and Rain Caps
Location of unit
For outdoor models, you must install a ue termination.
Instructions for mounting the ue termination are included
in this manual. Do not install outdoor models directly on the
ground. You must install the outdoor unit on a concrete, brick,
block, or other non-combustible pad. See Outdoor Installation
Venting. A wind proof cabinet protects the unit from weather.
is product contains a condensate
management and disposal system that
may be subject to freezing if exposed
to sustained temperatures below 32°F.
Precautions should be taken to protect the
condensate trap and drain lines during
extended periods of outdoor temperatures
below 32°F.
⚠WARNING
CAUTION
is unit is not intended for installations
where temperatures may reach below 32°F
(0°C). Exposure to freezing temperatures
will cause the system and appliance to
freeze and leak.
DIR #2000586797 00
36"
Figure 6-1 Outdoor installation