Control Panel Installation
Float Controls
Check the fl oats during their entire range of operation. Clean,
adjust, or replace damaged fl oats.
Checking the fl oat resistance - The fl oat resistance can be
measured to determine if the fl oat is operating correctly or is
defective. Use the following procedure to measure the float
resistance. Warning: Disconnect all incoming power to panel.
Failure to do so could result in serious or fatal electrical shock.
1. Isolate the fl oat by disconnecting one or both of the fl oat leads
from the fl oat terminals.
2. Place one ohmmeter lead on one of the fl oat wires, and the
other ohmmeter lead on the other fl oat wire.
3. Place the ohmmeter dial to read ohms and place on the R X
1 scale. With the fl oat in the “off” position, the scale should
read infi nity (high resistance). Replace the fl oat if you do not
get this reading. With the fl oat in the ON position, the scale
should read nearly zero (very low resistance). Replace the
fl oat if you do not get this reading.
NOTE: Readings may vary depending on the length of wire
and accuracy of the measuring device.
Fuses
Check the continuity of each fuse. With power OFF, pull the fuses
out of the fuse blocks. With the ohmmeter on the R X 1 scale,
measure resistance. A reading of infi nity indicates a blown fuse
and must be replaced. Replace fuse with same type, voltage and
amp rating.
Magnetic Contactor Coil
Warning: Disconnect all incoming power to panel. Failure to do
so could result in serious or fatal electrical shock. Check the coil
by disconnecting one of the coil leads. Measure the coil resistance
by setting the ohmmeter on the R X 1 scale. A defective coil will
read zero or infi nity, indicating a short or opened coil respectively.
Replace defective contactor with same type.
Control/Alarm Circuit
Board Power
If the green power
status indicators are not
illuminated:
1. Check to see if the
fuses on the circuit board are blown.
2. Check to see if the incoming control/alarm power is present
at TB1-1 and TB1-2.
If voltage is present and fuse is not blown, please call factory for
assistance.
Circuit Breaker (optional)
Check each pole of the circuit breaker for proper resistance reading
using the following procedure:
Warning: Disconnect all incoming power to control panel.
Failure to do so could result in serious or fatal electrical shock.
1. Isolate the circuit breaker by disconnecting either the line side
or load side wires.
2. Place the ohmmeter leads across the corresponding line and
load terminals of each pole.
3. With the ohmmeter on the R X 1 scale and the breaker in
the OFF position, the reading should be infi nity (very high
resistance). With the breaker in the ON position, the reading
should be nearly zero ohms (very low resistance). If the
readings are not as stated, replace the circuit breaker with
one of the same ratings.
Alarm Horn
Moving the test/normal/silence switch to the test position or
activating the alarm fl oat should turn on the alarm horn. If the horn
does not sound, replace horn with same type.
Alarm Light
Moving the test/normal/silence switch to the test position or
activating the alarm fl oat should turn on the alarm light. If the light
does not activate, replace with bulb of same type.
Troubleshooting
SJE-RHOMBUS
®
warrants to the original consumer that this prod-
uct shall be free of manufacturing defects for fi ve years after the
date of consumer purchase. During that time period and subject
to the conditions set forth below, SJE-RHOMBUS
®
will repair or
replace, for the original consumer, any component which proves
to be defective due to defective materials or workmanship of SJE-
RHOMBUS
®
.
ELECTRICAL WIRING AND SERVICING OF THIS PRODUCT
MUST BE PERFORMED BY A LICENSED ELECTRICIAN.
THIS WARRANTY DOES NOT APPLY: (A) to damage due to
lightning or conditions beyond the control of SJE-RHOMBUS
®
; (B)
to defects or malfunctions resulting from failure to properly install,
operate or maintain the unit in accordance with printed instructions
provided; (C) to failures resulting from abuse, misuse, accident, or
negligence; (D) to units which are not installed in accordance with
applicable local codes, ordinances, or accepted trade practices,
and (E) to units repaired and/or modifi ed without prior authorization
from SJE-RHOMBUS
®
.
Some states do not allow limitations on how long an implied warranty
lasts, so the above limitation may not apply to you. Some states do
not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specifi c legal rights, and you may also have
other rights which vary from state to state.
TO OBTAIN WARRANTY SERVICE: The consumer shall assume
all responsibility and expense for removal, reinstallation, and freight.
Any item to be repaired or replaced under this warranty must be
returned to SJE-RHOMBUS
®
, or such place as designated by
SJE-RHOMBUS
®
.
ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FIT-
NESS ARE LIMITED TO THE DURATION OF THIS WRITTEN
WARRANTY. SJE-RHOMBUS
®
SHALL NOT, IN ANY MANNER,
BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES AS A RESULT OF A BREACH OF THIS WRITTEN
WARRANTY OR ANY IMPLIED WARRANTY.
SJE-Rhombus
®
Five-Year Limited Warranty
NOTICE!
Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees
will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply.