Control Panel Installation

Operations
SJE-Rhombus
®
Type 122 panels are designed to op-
erate with three or four oats for pump sequencing. The
standard oat functions are common pump stop, lead pump
start, lag pump start/alarm (three oats), or separate lag and
alarm oats (four oats).
Three Float Operation: As the liquid level rises to the
stop oat and tips it to the ON (closed) position, the panel
will remain inactive. As the liquid level tips the lead oat,
the lead pump will start. If the liquid level tips the lag/alarm
oat, the lag pump will start and the audio/visual alarm will
activate. Both pumps and the alarm will remain active until
the liquid level drops and the lag oat is in the OFF (open)
position. At this time the alarm will silence. Both pumps will
remain on until the liquid level drops to normal and all three
oats are in the OFF (open) position. When both pumps have
stopped running, the alternator will switch the lead pump and
lag pump operating functions in the next sequence.
Four Float Operation: The alarm will activate and re-
main on only if the alarm oat is tipped to the ON (closed)
position.
Alarm System (Horn and Indicator - standard)
When an alarm condition occurs, a red light and a horn will
be activated. If the test/normal/silence switch is moved to the
silence position, the horn will be silenced. When the alarm
condition is cleared, the alarm system is reset. The alarm
system can be tested by moving the test/normal/silence
switch to the test position.
HOA Switch
A hand-off-automatic switch is provided for each pump. In
the hand mode, the pump will turn on unless other safety
features are employed. In the automatic mode, the pump
will turn on from commands by the oat switch(es).
Pump Run Lights
The run light will be ON in either the hand or the automatic
mode when the pump is called to run.
Control and Alarm Fusing
The control circuit and alarm circuit are fused separately.
For information regarding the
operations of options not listed here,
or servicing questions
please call a SJE-Rhombus
®
customer service technician at
1-800-RHOMBUS
(1-800-746-6287)
Warranty void if panel is modi ed.
Control and Alarm Lights
Lights will illuminate when control/alarm power is supplied.
Float Status Lights
Lights will illuminate when the respective oat is in the closed
position.
Circuit Breaker (optional)
The pump circuit has a thermal-magnetic circuit breaker
which provides pump disconnect and branch circuit protec-
tion.
Dry Auxiliary Contacts (standard feature)
Normally open - Contacts are open under normal conditions
and closed when alarm condition is present.
Normally closed - Contacts are closed under normal condi-
tions and open when alarm condition is present. Both types
automatically reset once alarm condition is cleared.
NOTE: Some options ordered may not be included in this
manual. Certain options will require alternative circuitry not
including oat status and control/alarm indicators.
FIGURE 5 - Mounting clamp detail
FIGURE 4 - Float with cable weight