Page 17
SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-I-091115
.
.
.......
..........
N
R
G
ER-1000HV
SENSING RESISTOR
200 K
600 VAC MAX
RATINGS:
MAXIMUM VOLTAGE
MAXIMUM CURRENT
RESISTANCE
THERMAL
600 Vac
3 mA
200 kΩ
600 Vac CONTINUOUS
40.0
(1.57)
105.0
(4.13)
4.5 (0.18) DIA
C’BORE 10.0 (0.39) DIA
3.2 (0.13) DEEP
8.0
(0.31)
41.5
(1.63)
22.2
(0.87)
40.0
(1.57)
10.5
(0.41)
10.5
(0.41)
19.0
(0.75)
NOTE 3
105.0
(4.13)
89.0
(3.50)
8.0
(0.31)
MOUNTING DETAILSIDE
FRONT
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.
3. MOUNTING SCREWS: M4 OR 8-32.
4. ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G
THROUGH JUMPER FROM TERMINAL G TO SCREW.
THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH
TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING.
Ω
FIGURE 13. ER-1000HV Sensing Resistor.