Installation Instructions

Installation Instructions
TFL
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
Part Number: RJ5210076 Rev B
Revision Date: 6/3/10
©2001 Acuity Brands Lighting, Inc.
All Rights Reserved. Rev. 06/10
Delivery: Upon receipt of fixture and accessories (packed separately), thoroughly inspect for any
freight damage. All damage should be reported to the delivery carrier. Compare the catalog
description listed on the packing slip with the fixture label on the inside of the housing to be sure
you have received the correct merchandise.
The standard fixture comes with a yoke mounting bracket which can easily be mounted to a variety
of accessory mounting hardware.
1. Mount floodlight to desired mounting hardware. (Figure 1).
2. Loosen the 2 stainless steel captive screws in front housing . (Figure 2).
3. Open front housing and allow to hang open. (Figure 3).
4. Run service wire through cord entry on bottom of housing. Make wire connections. For multi-tap ballast, refer to instructions below.
5. Lamp fixture as per instructions below.
6. Close front housing and tighten the 2 stainless steel captive screws.
Lamp Installation: Open doorframe. Verify that the lamp source and wattage corresponds with the fixture and ballast label. HID -Screw
the lamp securely into the socket, back it out one or two turns, and tighten securely again. This procedure properly seats the lamp in
the socket.
Troubleshooting: If this fixture fails to operate properly, check to make sure: The proper lamp is installed correctly. • The fixture is
wired correctly. • The lamp is not faulty. • The fixture is grounded correctly. • The line voltage at the fixture is correct.
Multi-tap Ballast (TB): The multi-tap ballast will be prewired for 277V at the factory. First determine the correct line voltage. Then
select the corresponding fixture voltage lead, remove the crimped cap and connect to the supply voltage lead. The fixture lead marked
COM should be connected to the neutral supply lead for 120 or 277. For 208 or 240, connect the other incoming hot leg to the fixture lead
marked "COM". Be sure to cap off all unused fixture leads individually.