Specification Sheet
TCLC
EMERGENCY: One Lithonia Way Conyers, GA 30012 Phone: 800-334-8694 techsupport-emergency@acuitybrands.com www.lithonia.com © 2010-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/04/20
TCLC Industrial Steel Emergency Lighting
Notes:
1. At 77°F (25°C).
2. All life safety equipment, including emergency lighting path of egress, must be maintained, serviced and tested in
accordance with all National Fire Protection Associate and local codes. Failure to perform the required maintenance,
service or testing could jeopardize the safety of occupants and will void all warranties.
3. Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher or lower temperatures
affect life and capacity.
Specifications
Electrical Primary Circuit
Input Watts (W) Input Amps (A)
120V 277V 120V 277V
TCLC
8.4 9.4
0.08A 0.04A
BATTERY
Sealed Lead-Acid
Type Voltage Typical Shelf Life Typical Life
1
Maintenance
2
Temperature Range
3
Emergency Light 6V 12 mos. 3-5 yrs none
68°F-122°F ( 20°C-50°C)
Example of single TCLC illuminating a 3' path of egress.
Example of multiple
TCLC luminaires illuminating
a 3' path of egress.
62'
1 FC average
3'
7.5'
3'
74'
1 FC average
Mounting
Height
Illumination
Level
Single Luminaire Multiple Luminaire
Application Notes
3' Path of
Egress
6' Path of
Egress
3' Path of
Egress
6' Path of
Egress
7.5' 1FC Avg 62' 56' 74
'
66
'
200' Corridor 8' wide,
and 12' high with
80/50/20 relfectances
10' 1FC Avg 54' 52' 66' 61'
200' Corridor 8' wide,
and 12' high with
80/50/20 relfectances
Maximum Spacing Guidelines - TCLC
1
1 Also meets the additional illumination requirements of NFPA 101: .1FC minimum and max/min ratio of 40:1.