Installation Guide
BATTERY
BLUE(-)
BLACK
ORANGE
277 VAC
120 VAC
NEUTRAL
BLACK
WHITE
TRANSFORMER
PCB BOARD
RED
YELLOW(+)
YELLOW(+)
BLUE(-)
+
_
LAMP LAMP
AC ON
TEST
Wiring Diagram
Part No. EMCSA00914 REV.A
7.15.2019
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE: 2 of 2
HO Wiring Diagram
2. If the charge indicator light is ON: Check that battery is properly connected. If problem persists, replace battery.
National Electric Code (NEC) and NFPA101 (current Life Safety Code) regulations require that routine tests need to be performed as
listed below:
Once every month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to perform this test.
Once every 12 months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect power to the unit and
leave it in the emergency mode. The lamps should stay ON for at least 90 minutes
lamps, as needed.
f � L L
®
-
An�rands Company
LIFE SAFETY SOLUTIONS
800-705-SERV {7378) www.lithonia.com