Cut Sheet
PHOTOMETRICS
STACK is compatible with Sensor Switch™
WSX-D and SPOD as well as nLight Wall Pods.
See STACK - Low-Profile Recessed LED Luminaire (acuitybrands.com) for photometry reports.
WSX-D
SPOD
ACCESSORIES
Accessories: Order as separate catalog number.
DGA24 Drywall grid adapter for 2x4 recessed fixture.
DGA22 Drywall grid adapter for 2x2 recessed fixture.
2X4SMKSHP PAF Multi-Use Surface Mount Kit 2X4 Post-Paint
2X2SMKSHP PAF Multi-Use Surface Mount Kit 2X2 Post-Paint
ILB CP10 A LED emergency battery pack, 10W 50VDC (Noncompliant with CA T20)
ILBLP CP10 HE SD A LED emergency battery pack, 10W Constant Power, Self-Diagnostic,
Certified in CA Title 20 MAEDBS
ELA PSRME IC Remote enclosure for battery for insulated ceiling
RK8BDP 2P U Disconnect Plug (BDP), 2 Pole, Package of 1
RK8BDP 3P U Disconnect Plug (BDP), 3 Pole, Package of 1
RK8BDP 2P J10 Disconnect Plug (BDP), 2 Pole, Package of 10
RK8BDP 2P J40 Disconnect Plug (BDP), 2 Pole, Package of 40
STACK LED Center Element Troffer
STACK
COMMERCIAL INDOOR: One Lithonia Way Conyers, GA 30012 Phone: 1-800-705-SERV (7378) www.acuitybrands.com © 2021-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/17/22
nLight WIRED
nPODMA DX
nLight AIR
rPODBA
Standby Mode Options
NOC Occupancy Sensor Disabled PWS1836 6’ pre-wire, 3/8” diameter, 18 gauge, 1 circuit
PWS1846 6’ pre-wire, 3/8” diameter, 18 gauge, 2 circuit
PWS1846 PWSLV Two cables: one 6' pre-wire, 3/8” diameter, 18 gauge, 2 circuits;
one 6' pre-wire, 3/8” diameter, 18 gauge ‡
PWS1856LV 6’ pre-wire, 3/8” diameter, 18 gauge, 1 circuit w/low voltage wires ‡
CP Chicago Plenum ‡
LATC T-bar clips
DWAM Anti-microbial paint
‡ Option Value Ordering Restrictions
Option Value Restriction
MIN1 Required for all Control Input options, excluding JOT. Not available with SLD.
Dimming If Control Input option selected leave this section blank
EZT Not available with MIN10
347 Not available with: E7W, E10WLCP, E15WLCP, SLD, GTD
SLD Not available with controls. Must select MIN10.
E7W, E10WLCP Not available with 347V
E15WLCP Not available with: 2X2 or 347V
GTD Must select 120 OR 277, Not available with 347V or MVOLT
NLTAIR2EM See UL924 Sequence of Operation Chart on page 3
JOT Not available with SLD, nLight, NLTAIR2, NOC, or GTD options. Must be ordered with COLT, not available with COL.
NOC Must select a Wireless Network Control
PWS1846 PWSLV, PWS1856LV Not available with nLight wired network or individual controls
CP Not available with Wired Network Controls, PWS1836, PWS1846, PWS1846 PWSLV or PWS1856LV.
UL924 Sequence of Operation
For 90 minutes following any complete AC power interruption >200 ms:
• Digital dimming is commanded to high end trim level.
• Device ignores wireless lighting control commands.