Cut Sheet
Power Sentry
1400 Lester Road, Conyers, GA, 30012
Phone: 888-300-7017
www.powersentrysafety.com
®
SPECIFICATIONS
BATTERY
Sealed Nickel-Cadmium
Voltage Shelf Life
1
Expected Life
1
Maintenance Optimum Temp
3
14.4 3 years 10 years none
2
32–100°F
Notes:
1 At 77°F.
2 Periodic system status test recommended.
3 Optimum ambient temperature range where unit will provide capacity for 90
minutes. Higher and lower temperatures affect life and capacity.
ELECTRICAL
Maximum AC input
Volts Amps Watts Power Factor
120 .092 9.6 .900
277 .041 10.19 .905
LAMP COMPATIBILITY
MOUNTING
All dimensions are inches (millimeters).
Cross section end view
Length: 15-3/8 (391mm)
Shipping weight: 10.3 lbs (4.7 kg)
PERFORMANCE
Emergency Lamp Lumen Output
Light output data based on one 32W T8 lamp. Two-lamp operation evenly divides
output between the lamps for better distribution of emergency illumination. Light
output of other lamp types will vary. Luminaire efficiency and application condi-
tions must be determined to calculate actual illuminance levels. Consult Lithonia
representative for further information.
KEY FEATURES
Remote mounting with the ELA PSDMT Remote Test Switch.
Accessory Kit.
PS3000 Emergency Ballast
5-5/8 (143)
2 (51)
3500
3000
2500
2000
10 20 30 40 50 60 70 80 90
L
U
M
E
N
S
MINUTES
Sheet #: PS3000
Type Description Length Wattage No. of Lamps
Linear
T5/T5HO 24"-48" 14-54 1
T8/T12 24"-48" 17-40 1 or 2
T8/T12 60"-96" 40-75 1
T12 HO/VHO 24"-96" 35-215 1
CFL (4-pin)
Twin-Tube N/A 18-50 1
Quad-Tube N/A 13-26 1
Triple-Tube N/A 26-32 1
Triple-Tube N/A 42 1
Other
T9 Circuline 20-40 1
Type Description 1 Lamp 2 Lamps
T5/T5HO
FP24T5/HO 1450 N/A
FP28T5 3100 N/A
FP54T5/HO 1900 N/A
T8
F17T8 2250 2000
F32T8 4000 3700
FB31T8 3750 3450
CFL
CF40 3650 N/A
CF26DT 1750 N/A
CF32TRT 2750 N/A
CF42TRT 3300 N/A
One-lamp emergency operation for 1 – 4
lamp ballasts.
Two-lamp emergency operation for 2 – 4
lamp ballasts.
INITIAL LUMEN OUTPUT TABLE