Technical Specifications

Catalog Number
Notes Type
FEATURES AND SPECIFICATIONS
INTENDED USE
Specication-grade emergency ballast operates one or two lamps (4' or shorter) or one 8' lamp.
Factory or eld installed within uorescent xture ballast channel. Upon interruption of normal power
battery pack automatically strikes and operates lamps at reduced light output, providing glare-free
illumination for 90 minutes.
CONSTRUCTION
Durable thermoplastic/metal housing resists impact, scratches, and corrosion. UL-94V-0 ame rating
Reduced-prole footprint ts in the tightest applications
Polarized quick-connect pilot light/test switch assembly simplies installation
Pilot light and test switch provide visual and manual means of monitoring system operation
U.S. Patent No. 6,522,147; 5,814,971; 6,577,136; D550,154
PERFORMANCE
Lamp selector switch optimizes single or dual lamp performance
Operates one or two 2'–4' uorescent T8–T12 lamps, one 2'–4' uorescent T5, T8, or T12, HO, long
compact (biax) or one 6'–8' uorescent T8–T12 for 90 minutes. Compatible with T8 and T5 electronic,
T12 magnetic, instant start, rapid start, and slimline ballasts. New AC ballasts with EOL (end of life)
protection may require EOL accessory (ELA PSPRSB) to ensure normal AC mode operation
ELECTRICAL
Multi-voltage input capability (120V-277V; 50-60 Hz)
Constant current-type charger. Input circuit provides high eciency and reliable operation
High-eciency push-pull inverter is the most eective method of converting DC power to AC power.
It provides maximum light output, battery life and reliability
BATTERY
Sealed, maintenance-free, high-temperature nickel-cadmium battery. Ensures long life over a wide
range of temperatures
Automatic battery recharge after 90-minute discharge. Fully charged after 24 hours
INSTALLATION
Patented Quick-Disconnect connector system allows for quick and easy replacements at end of life
without rewiring
Mounts concealed within xture wireway for clean appearance and protection against vandalism;
or mounts on outside of xture housing if internal space is limited. Two 1/2" holes in xture channel
permit mounting of test switch/pilot light behind xture lens
External mounting requires a remote mounting enclosure (ELA PSRME).
Compact size (13-5/16" L x 2-3/16" W x 1-3/16" H) ts in a variety of uorescent xtures: troers,
volumetric recessed, industrials, commercials and strips
Unit wires two ways: on night light circuit (permanently energized) or on switchable circuit
(unswitched circuit to battery charger and switched circuit to the xture ballast). Unit will strike
normally o lamp
Unit mounting centers are identical to a standard ballast
1 of 2One Lithonia Way Conyers, GA 30012 Phone: 888-300-7017 www.powersentrysafety.com ©1997-2014 Acuity Brands Lighting, Inc. All rights reserved 3/10/14
1400 Lumen Reduced-Prole
PS1400QD MVOLT
Emergency Ballast
Options Accessories
4
Series
PS1400QD MVOLT Blank
SD
Emergency ballast Standard
Self-diagnostics
1,2,3
Example: PS1400QD MVOLT SD
NOTES
1 Self-diagnostics (PSSD) module ships separately. See PSSD Inverter Accessories
spec sheet for details on self-diagnostics.
2 Compatible with lamp EOL protection ballasts.
3 ELA PSPRSB not required with SD option.
4 See Inverter Accessories specication sheets for details on other compatible
devices ELA-RTS-TSPLP-PSTS-PSPRSB and ELA-PSMK-PSMKSD-PSDMT-PSRME
ORDERING LOGIC
For shortest lead times, congure product using standard options (shown in italics).
PS1400QD MVOLT
Order as separate item.
ELA TSPLP Remote or replacement test switch pilot light; mounts up to 25' away from xture
ELA TSPLPSD Remote or replacement test switch pilot light for self-diagnostics; mounts up to 25' away from xture
ELA PSMKSD External mounting kit for self-diagnostics module
ELA PSRME External mounting box enclosure PS300QD, PSQ500QD, PS600QD and PS1400QD
ELA PSPRSB Field-installabe interface for enhanced compatibility with lamp EOL protection ballasts
3
PSSD Field-installable self-diagnostics module
LISTING
UL listed. Meets UL 924, NFPA 101 (current Life Safety Code), NEC and OSHA illumination standards
Standard unit is UL approved for installation in sealed and gasketed xtures
See PS1400DW specication sheet for product UL approved for use in wet and damp location xtures
WARRANTY
Five-year limited warranty. Complete warranty terms located at www.acuitybrands.com/
CustomerResources/Terms_and_conditions.aspx
Actual performance may dier as a result of end-user environment and application.
Note: Specications subject to change without notice
H  13/16"
W  23/16"
L  135/16"