Technical Specifications

1 of 2
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2014-2015 Acuity Brands Lighting, Inc. All rights reserved. 05/20/15
OVERVIEW
The MP20 power/relay pack and MSP20 secondary relay pack work with low voltage occupancy
sensors to switch lighting loads on and off. The MP20 also transforms 120, 240, and 277 VAC
single phase power to Class 2 15 VDC to power remote sensors. Although plenum rated, the
elongated mounting nipple allows for these packs to be mounted either directly through a 1/2
inch knockout in a junction box, or to be located inside an adjacent box for specific local code
requirements. Up to 14 sensors may be connected to one MP20. Multi-circuit control can be
handled by multiple MP20 or MSP20 packs. MP20s can be wired continuously hot (line side),
or on the switch leg (load side) without nuisance delays upon turn on.
FEATURES
Powers Low Voltage Sensors (MP20)
Switches Line Voltage Loads
Plenum Rated
MP20
MSP20
ORDERING INFORMATION
MP20 Example: MP20 LT
Series Temperature/Humidity
MP20 Power/ Relay Pack
MSP20 Secondary Relay Pack
[blank] Standard
LT Low Temp
Size: (not including chase nipple) 3.00” H x 2.25” W x 1.88” D
(7.62 cm x 5.72 cm x 4.78 cm)
Weight: 6 oz
Mounting: 1/2” knockout
Color: Black
Operating Voltage: 120, 240, 277 VAC (single phase)
Relay Current Reqs: 40 mA
Switching Load: 20 Amps
Output Voltage/Current: 15 VDC, 150 mA at 120 or 277 VAC (MP20)
Motor Load: 1 HP
Max. humidity: 2090% non-condensing
Ambient temperature: 14–160° F (-10–71° C)
ROHS compliant
SPECIFICATIONS
Warranty
Five-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.