Installation & Assembly
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
SURFACE MOUNT EDGE-LIT LED EXIT SIGN
Standard & New York Approved Model
(Emergency, non-Emergency and X2 Dual Circuit operations)
INSTALLATION (BACK MOUNT):
1. Mount canopy to junction box (or spider plate if required) using the two recessed mounting holes and two (2) 1½” #8-32 screws.
2. Run connection wires through large hole in center of canopy.
3. Secure fi xture to canopy with two (2) ¾” #10-24 screws (included) by going directly into mounting holes A and C.
4. Make electrical connections.
TESTING:
National Electric Code (NEC) and NFPA life safety code regulations require that routine tests need to be performed as listed below:
Once every month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to perform this test.
Once every 12 months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect power to the unit and
leave it in the emergency mode. The lamps should stay ON for at least 90 minutes.
OPERATION:
CAUTION: EL Operation: The battery in this unit may not be fully charged. After electricity is connected to unit, let battery charge for at
least 24 hours, then normal operation of this unit should take effect.
1. Apply AC power to the sign. The LED Indicator should turn RED.
2. EL Operation: After the battery has been left to charge for 2 hours, test the sign by pushing the switch. The LED indicator turns
OFF and the sign should remain ON.
3. When the switch is released, EXIT section remains ON and the LED indicator turns back to RED.
MAINTENANCE:
Caution: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a qualifi ed service techni-
cian. Use only MANUFACTURER supplied replacement parts.
1. BATTERY: The battery supplied in this equipment requires no maintenance. However, it should be tested periodically (see TEST-
ING) and replaced when it no longer operates the connected fi xtures for the duration of a 30-second or 90-minute test. The battery
supplied in this equipment has a life expectancy of 5-7 years when used in a normal ambient temperature of 72°F.
2. OTHER: Clean exit panel with non-abrasive cloth and cleaner when required.
WIRING DIAGRAMS:
NOTE: Unused input lead must be properly insulated with wire nut or other approved method.
TRANSFORMER
LED BOARD
RED 277VAC
BLACK 120VAC
WHITE COMM
Battery
TRANSFORMER
LED BOARD
RED 277VAC
BLACK 120VAC
WHITE COMM