OPERATION (BATTERY BACKUP)
1. Apply AC power to the unit. The LED indicator will be RED.
2. After the battery has been left to charge for 24 hours, test the unit by pushing the switch. The LED indicator turns
OFF and the LED board stays ON.
3. When the switch is released, the LED indicator turns back to RED and the LED board stays ON.
MAINTENANCE
IMPORTANT CODE COMPLIANCE INFORMATION
Caution: Always turn off AC power to the equipment before servicing. Servicing should be performed only
by a qualified service technician. Use only MANUFACTURER
supplied replacement parts.
BATTERY : The battery supplied with the EL model requires no maintenance. However, it should be tested periodically
and repl
aced when it no longer operates the connect
In accordance with NFPA 101, documented testing of your emergency lighting system must be tested monthly for a
minimum of 30 seconds and annually for 90 minutes. Refer to your local codes for any additional requirements that
may apply.
ed sign for the duration of a 30-second or 90-minute
test. The battery supplied in this sign has a life expectancy of 5 years when used in a normal ambient
tempe rature of 72° F.
PART # EMCSA00803 (REV A)
SAVE THESE INSTRUCTIONS
Lithonia Emergency
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694 Fax: 770-981-8141
www.lithonia.com