Installation Guide

Table Of Contents
INSTRUCTIONS for Lithonia Lighting EXRG
800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
Part No. 912-00194-001,
Rev A Prelim 10.19.2020
OPERATION (BATTERY BACKUP)
1. Apply AC power to the unit. The LED indicator will be RED.
2. After the battery has been left to charge for 24 hours, test the unit by pushing the switch. The LED indicator turns
OFF and the LED board stays ON.
3. When the switch is released, the LED indicator turns back to RED and the LED board stays ON.
MAINTENANCE
Caution: Always turn off AC power to the equipment before servicing. Serving should be performed only
by a qualified service technician. Use only MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied with the EL model requires no maintenance. However, it should be tested periodically
and replaced when it no longer operates the connected sign for the duration of a 30-second or 90-minute
test. The battery supplied in this sign has a typical life of 5 years when used in a normal ambient temperature
of 72°F.
SAVE THESE INSTRUCTIONS
In accordance with NFPA 101 (current Life Safety Code), documented testing of your emergency lighting system
must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to your local codes for any
additional requirements that may apply.
SAVE THESE INSTRUCTIONS
and deliver to owner after installation