Specification Sheet

EU2C Emergency Light
EU2C
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 09/05/19
Pg. 2 of 2
Maximum Spacing Guidelines — EU2C
1
Mounting
Height
Illumination
Level
Single Luminaire Multiple Luminaires
Application
Notes
3' Path of
Egress
6' Path of
Egress
3' Path of
Egress
6' Path of
Egress
7.5' 1FC Avg 10' 6' 14' 11'
100' Corridor
8' wide, and 9'
high with
80/50/20
reflectances
Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio
of 40:1.
*Note: To see complete photometric report or download the .ies file for this product,
visit Lithonia Lighting EU2C home page.
SPACING GUIDELINES
Example of single EU2C illuminating a 3' path of egress.
Example of multiple
EU2C luminaires
illuminating a 3' path
of egress.
3'
14'
1 FC average
10'
1 FC average
3'
7.5'