Specification
One Lithonia Way, Conyers, GA 30012 | 800-705-SERV (7378) | techsupport-emergency@acuitybrands.com | www.lithonia.com
© 2019-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 08/11/22
Page 2 of 2
CONTRACTOR SELECT EU2C
INTENDED USE:
Provides a minimum of 90 minutes illumination for the rated wattage upon loss of AC power
to meet code required emergency lighting. Ideal for applications requiring low prole,
emergency unit for lower mounting heights.
CONSTRUCTION:
Injection-molded, ame-retardant, high-impact, thermoplastic housing with snap-t design
components with LED lamps for easy installation. Universal J-box pattern (j-box not included).
Track and swivel arrangement permits full range of lamp adjustment.
OPTICS:
The typical life of the LED is 10 years. Two 1W LED Lamps.
ELECTRICAL:
Multi volt input,120-277VAC, 50/60Hz. Emergency unit provided with test switch, status
indicator and rechargeable battery. Maintenance-free 3.6V nickel-cadmium battery provides
90 minutes of emergency power.
INSTALLATION:
Wall mount only (not suitable for ceiling mount).
LISTINGS:
UL Listed. Meets all applicable requirements for UL 924, NFPA 101 (current Life Safety Code),
NFPA 70 (NEC), California Energy Commission Title 20 section 1605.3 (W)(4), FCC and OSHA.
Indoor damp location 50°F to 104°F (10°C to 40°C) listed standard.
WARRANTY:
2-year limited warranty. This is the only warranty provided and no other statements in this
specication sheet create any warranty of any kind. All other express and implied warranties
are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/
warranty/terms-and-conditions
Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specications subject to change without notice.
Specifications Dimensions
Weight (shipping): 1.7 lbs. (0.77 kgs.)
All dimensions are inches (centimeters) unless otherwise indicated.
Maximum Spacing Guidelines - EU2C
1
Mounting
Height
Illumination
Level
Single Luminaire Multiple Luminaires
Application
Notes
3' Path of
Egress
6' Path of
Egress
3' Path of
Egress
6' Path of
Egress
7.5' 1FC Avg 10' 6' 14' 11'
100' Corridor
8' wide, and
9' high with
80/50/20
reflectances
Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio
of 40:1.
10-1/8
3-3/4
(9.5)
5-3/8 (13.7)
14-5/8
3-3/4
(9.5)
2
(5.1)
10-1/8
3-3/4
(9.5)
5-3/8 (13.7)
14-5/8
3-3/4
(9.5)
2
(5.1)
Example of single EU2C illuminating
a 3' path of egress.
Example of multiple
EU2C luminaires
illuminating a 3' path
of egress.
3'
14'
1 FC average
10'
1 FC average
3'
7.5'
Spacing guidelines