Installation Guide

INSTALLATION INSTRUCTIONS
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE: 3 of 3
TESTING:
NFPA 101 Life Safety Code requires that all emergency lighting equipment be functionally tested every 30 days for a
minimum of 30 seconds and tested annually for a full 90-minute duration. Written records of the testing are to be kept for
examination by the authority having jurisdiction.
TROUBLESHOOTING:
1. The emergency lights DO NOT operate and:
a. If the charge indicator light is OFF - Check that the circuit breaker for AC supply is ON.
b. If the charge indicator light is ON:
- Check that the battery is properly connected
- If remote lamps are connected to the equipment, then turn OFF the AC supply and disconnect the remote circuit wires from the
equipment. Turn ON the AC supply and depress the test switch. If the local lamps (mounted on the equipment itself) come ON, then
check the remote circuit for short or overload condition and correct as required. Reconnect the circuit wires and restore AC power.
- If the local lamps don’t turn ON after disconnecting the remote circuit wires, then replace battery.
2. Emergency lights are dim - Implies battery might not be fully charged. Allow battery to recharge for 24 hours and then re-test.
3. Remote lights are dim - Remote wire size is too small causing excessive voltage drop (more than the permitted 5%) and thus causing the
lamps to illuminate with less intensity. Refer to STEP 4 of INSTALLATION section for more information.
Part #EMCSA00786 Rev. F
2017.06.20
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com