Specification
ELSQ-M-
EMERGENCY One Lithonia Way Conyers, GA 30012 Phone: 800-334-8694 Fax: 770-981-8141 www.lithonia.com ©1997-2012 Acuity Brands Lighting, Inc. All rights reserved. Rev. 12/11/12
ELSQ/ELSQM Emergency Square Series
DIMENSIONS
All dimensions are inches (centimeters).
SPECIFICATIONS
Shipping Weight: ELSQ 5 lbs. (2.3 kgs.)
ELSQM 6.5 lbs. (3 kgs.)
KEY FEATURES
Fully-recessed mounting accessory kit – ELA FRK.
(1/4" rough-in opening)
10-3/8
(26.4)
1-9/16
(4.0)
3-1/2
(8.9)
10-3/4
(27.3)
10-3/4
(27.3)
1-1/4
(3.2)
1-1/4
(3.2)
3-5/16
(8.3)
3-1/2
(8.9)
9
(22.9)
9
(22.9)
10-3/8
(26.4)
1
(2.5)
4-1/2
(11.4)
4-1/2
(11.4)
7/16
(1.1)
(1/4" rough-in opening)
FULLY-RECESSED (accessory kit)
RECESSED MOUNTING BOX
HOUSING BACK
NOTES
1 Watts to 87-1/2% of 6V.
2 At 77°C (25°C).
3 Optimum ambient temperature range where unit will provide rated capacity for 90 minutes. Higher and lower
temperatures aect life and capacity. Consult factory for more details.
4 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced, and tested
in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required
maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties.
ELECTRICAL
Primary Circuit
AC Input Output Volts Watts Ouput
1
Type Volts Amps Watts 1-1/2 hrs. 2 hrs. 3 hrs.
ELSQ 120 .167 10 6 10 - -
277 .072 10
ELSQM 120 .167 20 6 20 16 10
277 .072 20
BATTERY
Sealed Lead-Calcium
Voltage Shelf life
2
Typical life
2
Maintenance
4
Optimum Temperature
3
6 12 mos. 5-7 yrs. none 60°-90°F (16°-32°C)
BATTERY
Sealed Nickel-Cadmium
Voltage Shelf life
2
Typical life
2
Maintenance
4
Optimum Temperature
3
6 3 yrs. 7-9 yrs. none 32
0
-100
0
F (0°-38°C)
Rated Output Capacity in Watts - Emergency Run Time
1.5 hrs. 2 hrs. 3 hrs.
ELSQ N 10
--
--
ELSQM N 20 15 10