Installation Guide

INSTALLATION INSTRUCTIONS
WIRING DIAGRAMS
Part #EMCSA00764 Rev. F
2015.04.27
NOTE for HO models:
Use of 10-12 AWG stranded wire required to connect remote lamp heads to maintain operating voltage when remote xtures are connected to the emergency lighting equipment.
IMPORTANT CODE COMPLIANCE INFORMATION
In accordance with NFPA 101, documented testing of your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer to
your local codes for any additional requirements that may apply.
NOTE: Unused input
lead must be properly
insulated with wire
nut or other approved
method