Installation Guide

INSTALLATION INSTRUCTIONS
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
LED COMBO EXIT & EMERGENCY LIGHT (cont.)
MAINTENANCE:
CAUTION: Always turn off AC power to the equipment before servicing. Servicing should be performed only by a quali ed
service technician. Use only MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied with the EL model requires no maintenance. However, it should be tested periodically and
replaced when it no longer operates the connected sign for the duration of a 30-second or 90-minute test. The battery sup-
plied in this sign has a life expectancy of 5 years when used in a normal ambient temperature of 72° F.
WIRING DIAGRAM:
PAGE: 3 of 3
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com
Part #EMCSA00802 Rev. E
2017.08.09
HIGH OUTPUT
BLUE(-)
TEST
LAMP
BLUE(-)
YELLOW(+)
+
-
YELLOW(+)
To Remote Head
LAMP
BLUE(-)
YELLOW(+)
TRANSFORMER
PCB/LED BOARD
BATTERY
RED(277V)
BLACK(120V)
WHITE(COM)
"READY" LIGHT
REGULAR
TRANSFORMER
TEST
LAMP
BLUE(-)
YELLOW(+)
+
-
LAMP
BLUE(-)
YELLOW(+)
PCB/LED BOARD
BATTERY
RED(277V)
BLACK(120V)
WHITE(COM)
"READY" LIGHT