Installation Guide
INSTALLATION INSTRUCTIONS
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
LED COMBO EXIT & EMERGENCY LIGHT
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING:
FAILURE TO FALLOW THESE INSTRUCTIONS AND
WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT
PROPERTY DAMAGE. For your protection, read and follow these warnings
and instructions carefully before installing or maintaining this equipment.
These instructions do not attempt to cover all installation and maintenance
situations. If you do not understand these instructions or additional
information is required, contact LITHONIA or your local LITHONIA distributor.
WARNING:
RISK OF ELECTRIC SHOCK - NEVER CONNECT TO,
DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
WARNING: RISK OF FIRE. Lamps are hot. Keep combustible
material away from hot parts. Observe lamp manufacture’s warnings,
recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.
CAUTION: The battery in this unit may not be fully charged. After electricity is connected to unit, let battery charge for at least 24
hours, then normal operation of this unit should take effect. To check, press the TEST button. The lamps on the unit should turn on.
IMPORTANT SAFEGUARDS: When using electrical equipment, basic safety precautions should always be followed, including the following:
• Do not use outdoors.
• Consult local building code for approved wiring and installation.
• Disconnect AC power before servicing and installation.
• Do not mount near gas or electric heaters.
• Do not use this equipment for anything other than its intended use.
• The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition.
• Any service on this equipment should be performed by qualifi ed personnel only.
• Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
• Use caution when servicing batteries.
• Cap unused wires with enclosed wire nuts or other approved method.
• Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels
NOTE: Max mounting height is 8.5 ft to achieve at least 1 ft-candle of illuminance
in emergency mode.
INSTALLATION INSTRUCTIONS (back mount):
1. Remove EXIT stencil from housing, set aside.
2. Drill or knock out appropriate knockouts on back plate to fi t junction box mounting points.
3. Drill or knock out center hole in back plate for EXIT supply wire leads.
4. Route EXIT supply wires through center hole of the back plate and make wiring connection. For 120V, use black and white wires and
for 277V, use red and white wires. WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved means.
5. Secure back plate to junction box (hardware not included).
6. Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier
access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel, securing with diffuser
retention caps once chevron(s) have been removed.
7. Connect battery only after continuous AC power can be provided to the unit.
8. Apply continuous AC power and press “TEST” button to check operation.(See operation (battery back-up) for testing procedures)
PAGE: 1 of 3