Installation Guide
Page 7 of 14
U351 Rev. J 03/10/2020
LED IMPORTANT SAFETY INSTRUCTIONS
For Continuous Row
5) For STD configurations, Remove Housing End Cap(s) with one screw and disengage end cap snap features. For L/EP option, fixture
shipped without endcaps for ease of continuous row mounting. WARNING - Fixtures at end of row must have Housing End Caps
installed, as shown below. Housing End Caps can be ordered using nomenclature CLXEPxx xxxx. Failure to install Housing End
Caps is a safety hazard.
6) If supplied with a PLR (continuous row wiring), pull PLR connector from fixture. Male will be located on the access plate side.
7) Attach Continuous row mounting bracket into fixture A (supplied with fixture) by snapping into the driver channel and attaching
two screws provided in hardware bag.
8) If using a PLR continuous row wiring system, connect female PLR plug from fixture B into the Male PLR plug from fixture A.
9) Snap fixture B into the continuous row bracket and attach using the remaining two screws from the hardware bag.
Without Sensor – Continuous Row
Step 5 Step 7 Step 9
Sensor Version – Continuous row
Use caution to not damage sensor lens
Included
in Box
Threaded assembly
Aircraft cable