Installation Manual

MOTION SENSOR
INSTALLATION
7. To set sensor functionality, remove screw
from plastic cover on sensor and then
unscrew top cover from sensor assembly.
You will see dip switch.
MC031V SENSOR SETTINGS
By setting the DIP switch, sensor data can be precisely set for each specific application.
Detection area
Detection area can be reduced by selecting the appropriate
combination on the DIP switches.
Factory default settings
Hold Time
Sets the time period the lamp remains at 100% illumination after
no motion detected.
ON
1
I ON 100%
II 50%
ON
2 3 4
I ON ON ON 5s
II ON ON 30s
III ON ON 90s
IV ON 3min
V ON ON 20min
VI 30min
1 2 3 4 5 6 7 8 9 10 11 12
ON
ON ON ON ON - - - - - ON ON ON
Stand-by period
Controls the time period the lamp remains at a low light level before it
completely switches off in the long absence of people. When set to +∞,
the low light is maintained until motion is detected.
ON
5 6 7
I ON ON ON +∞
II ON ON 60min
III ON ON 30min
IV ON 10min
V ON ON 5min
VI 5s
6