SP4000 Flow Computer
6.8
FLOW INPUT
(Continued)
FLOW INPUT
Select the type of square law flowmeter to be used with the
instrument.
Note:
This selection will only appear if one of the Square Law
selections were made in "FLOWMETER TYPE".
Selection:
ORIFICE, V-CONE, ANNUBAR, PITOT, VENTURI, FLOW
NOZZLE, BASIC SQRLAW/TARGET, WEDGE
Display: ORIFICE
SQUARE LAW FLOWMETER
Select the type of measuring signal produced by the flowmeter.
Selection:
DIGITAL, 10 mV LEVEL Voltage pulses, 10mV
trigger threshold.
DIGITAL, 100 mV LEVEL Voltage pulses, 100mV
trigger threshold.
DIGITAL, 2.5 V LEVEL Voltage pulses, 2.5V trigger
threshold.
4-20 mA 4-20 mA current signal
0-20 mA 0-20 mA current signal
4-20 mA STACKED 4-20 mA current signal
0-20 mA STACKED 0-20 mA current signal
0-5 V 0-5 V voltage signal
1-5 V 1-5 V voltage signal
0-10 V 0-10 V voltage signal
Display: 4-20 mA
INPUT SIGNAL
Set the low scale value for the analog input signal.
The value entered here must be identical to the value set for the
flowmeter.
Note:
For flowmeters with analog/linear output, the flow computer
uses the selected system units for volumetric flowrate.
The units for differential pressure flowmeters are
dependent on the system units selected for pressure:
- Imperial units [inches H2O]
- Metric units: [mbar]
Input:
Number with floating decimal point: 0.000...999999
Display: .000 ft3/h
LOW SCALE VALUE
SQUARE LAW
FLOWMETER
INPUT SIGNAL
LOW SCALE