Manual

21
SP4000 Flow Computer
3.9 Steam Mass
Measurements:
A flowmeter measures the actual volume flow in a steam line. A temperature and/or
pressure sensor is installed to measure temperature and/or pressure.
Calculations:
Density and mass flow are calculated using the steam tables stored in the flow
computer.
Saturated steam requires either a pressure or temperature measurement with the
other variable calculated using the saturated steam curve.
Optional steam trap monitoring using Compensation Input 1.
Input Variables:
Superheated Steam:
Flow, temperature and pressure
Saturated Steam:
Flow, temperature or pressure
Output Results:
Display Results
Mass or Volume Flow Rate, Resettable Total, Non-Resettable Total,
Temperature, Pressure, Density (optional: peak demand, demand last hour,
time/date stamp)
Analog Output
Mass or Volume Flow Rate, Temperature, Pressure Density, Peak Demand,
Demand Last Hour
Pulse Output
Mass or Volume Total
Relay Outputs
Mass or Volume Flow Rate , Total, Pressure, Temperature, Alarms, Peak
Demand, Demand Last Hour
Applications:
Monitoring mass flow and total of steam. Flow alarms are provided via relays and
datalogging is available via analog (4-20mA) and serial outputs.
STEAM MASS
Steam Mass
Illustration
714
Flowmeter
Condulet
Temperature
Transmitter
PRINT
5
0
TIME
CLEAR
MENU
ENTER
HELP
TEMP
4
PRE 1
3
RATE
2
TOTAL
1
GRAND
6
SCROLL
7
PRE 2
8
DENS
9
Pressure
Transmitter
Mass Flow
Mass Flow = volume flow density (T, p)
Calculations