SP4000 Flow Computer
20
3.8 Liquid Delta Heat
Measurements:
Actual volume flow is measured by the flowmeter. Temperature of the supply and return
lines are measured by the temperature transmitters.
Calculations:
The density, mass flow and delta heat are calculated using values of the heat carrying
liquid stored in the flow computer. (see "FLUID DATA" submenu)
Output Results:
Display Results
Heat, Mass or Volume Flow Rate, Resettable Total, Non-Resettable Total,
Temperature1, Temperature2, Delta Temperature, Density, (optional: peak
demand, demand last hour, time/date stamp)
Analog Output
Heat, Mass or Volume Flow Rate, Temperature1, Temperature2, Delta
Temperature, Density, Peak Demand, Demand Last Hour
Pulse Output
Heat, Mass or Volume Total
Relay Outputs
Heat, Mass or Volume Flow Rate, Total, Temperature Alarms, Peak Demand,
Demand Last Hour
Applications:
Calculate the energy which is extracted by a heat exchanger from heat carrying liquids.
LIQUID DELTA HEAT
Liquid Delta Heat
Illustration
Water
Heat = Volume Flow ρ(T1) [h(T
2
) h(T
1
)]
Other heat carrying liquids
Heat = C volume flow (1-α (T
1
-T
ref
))
2
ρ
ref
(T
2
- T
1
)
WHERE: Delta T > Low Delta T Cutoff
α = Thermal expansion coefficient 10
-6
C = Mean specific heat
ρ(T1) = Density of water at temperature T
1
h(T1) = Specific enthalpy of water at temperature T
1
h(T2) = Specific enthalpy of water at temperature T
2
ρ
ref
= Reference density
T
ref
= Reference temperature
Calculations
Flowmeter
T2
Temperature
Transmitter
PRINT
5
0
TIME
CLEAR
MENU
ENTER
HELP
TEMP
4
PRE 1
3
RATE
2
TOTAL
1
GRAND
6
SCROLL
7
PRE 2
8
DENS
9
T1
Temperature
Transmitter
Water
Warm
Cold