61
SET BAUD
Format:: SET BAUD [nnnn] (CR)
Function: Sets the baud rate to the value specified in nnnn. nnnn may be 300, 1200, or 9600. The
baud rate is immediately set to the value specified.
NOTE: 300 baud may cause undesirable delays in communication.
Example: SET BAUD 1200 (CR)
SET EXCEPTION:
Format:: SET EXCEPTION [ON, OFF] (CR)
Function: Turns Exception Reporting ON or OFF.
Exception Reporting is a function that allows the operator to view different parameters that have recently gone into
alarm condition (See section on Exception Reporting in this chapter).
Example: SET EXCEPTION on (CR)
SET LIST:
Reference: See Section 8.2
Format:: SET LIST n n n n (CR)
Where n is the number of an item on the display list
Function: The SET LIST command is used to set up a display list which can be periodically printed at
a remote terminal or printer. The user would first type EXAMINE LIST to obtain a list of
available display items, and would then use the SET LIST command to enter them into a
printable list of items.
Example: MFC01 Examine List (CR)
[SELECT items from this list:]
[1] Time & Date
[2] Flow rate
[3] Totalizer
[4] Temperature
[5] Pressure
[6] Uncompensated Flow
[7] Raw Flow (Chan 3)
[8] Raw Temp. (Chan 1)
[9] Raw Press. (Chan 2)
[10] Analog Output
MFC01
NOTE: List will vary depending on Hardware and Computation Selected.
Then, the user selects time, flow rate, totalizer, and pressure by typing:
MFC01 SET LIST 1 2 3 5 (CR)
Then when the instrument is running and the PRINT INTERVAL is greater than 0.24999 minutes the instrument will
show:
11:55:52 Monday April 28, 1992
Flow Rate 10,000 SCFM
Totalizer 1245.000 cu-ft
Pressure 12.000 PSIG