User Manual

38
DIAGNOSTICS - ERROR MESSAGES
POWER FAIL ERROR
The fueling ended due to a loss of input voltage greater than 15 seconds. This message is displayed if power is
removed during a fueling. Ensure that power was not turned off manually, then check the power supply, the wiring and
the in-line fuse. See the troubleshooting section for more information. See page 45.
PRESET ERROR
When accessing a preset eld, a ash memory error was detected. If this error persists, contact a LC service provider.
DATA ACCESS ERROR
A ash memory error occurred. If this error persists, contact a LC service provider.
INIT WARNING
This message appears when the No-Flow Timer or the Ticket Required? eld return an error. If this error
occurs, the fueling can continue but default values 180 and Yes are used. If this error persists, contact a LC service
provider.
RUN TIME ERROR MESSAGES
These messages may be displayed if an error occurs while the system is
running.
Invalid entry or value out of specied range
The value entered into the text box is outside of the range specied for
the eld. Reenter the value.
FLASH CRC FAILURE
The CRC stored with an LCR 600 data block indicates the data or CRC
has been corrupted. A rebuild operation could possibly x the problem.
If not, try a clear all (contact a LC service provider). If that does not
work, hardware may be at fault and the unit should be returned to Liquid
Controls for more analysis. Before starting a clear all operation, print a
calibration ticket.
FLASH WRITE FAILURE
A failure detected while a data block was being written to the ash memory. See Flash CRC Failure above for
corrective actions.
FLASH NOT INITIALIZED
The selector switch was not in the CALIBRATION position when a Clear All or Rebuild was attempted.
Duplicate ow rates not allowed
This message only appears when setting up multi-point calibration. When calibrating a multi-point owmeter, each
linearization point must have a unique ow rate. This message is displayed if a duplicate ow rate is entered.
Adjacent linearization points out of 0.25% range
This message only appears when setting up multi-point calibration. When calibrating a multi-point owmeter, adjacent
linearization points must be within a 0.25% correction of each other. To avoid this error, select an additional ow rate
and correction factor between the two points. More than one additional point may be required.
Invalid logon parameters
FlightConnect
The Fueler ID and/or password entered does not exist in FlightConnect’s Fueler database. Enter a valid Fueler ID.
Invalid parameter
FlightConnect
A RUN command was issued and a required parameter (fueling detail) is missing. Enter the required parameter. Then,
FlightConnect will allow the fueling to start.
Invalid entry
FlightConnect
The value entered does not meet the requirements of the eld. This error often appears when a required eld is left
blank. Enter the proper data.
There was no response from the LCP device.
FlightConnect
The LCR 600 attempted to retrieve data from the ofce, but can not connect. Retry. If the error persists, check the
transmission device on the vehicle. If the error still persists, check the ofce computer and ofce transmission device.
If the problem still persists, make sure that DBManager and FlightConnect Read are running and congured properly.
SYSTEM SETUP 1
Meter ID:
Unit of Measure:
Decimal Digits:
Residual Processing:
Flow Rate Base:
A101
GALLONS
TENTHS
ROUND
PER MINUTE
dP Shutdown Value
250
LCP02SetField: 113
Invalid entry or value is out of
specified range.