To single point calibrate a product, the LCR 600 must make a fueling into a volumetric prover. The measurement
indicated by the volumetric prover is then entered into the LCR 600. This sets the k-factor (pulses/unit). The new
k-factor establishes the number of pulses the LCR 600’s internal pulser registers for each unit of measurement that
passes through the owmeter (for example, 205.8 pulses for every gallon). When proving for use in Weights and
Measures applications, a qualied Weights and Measures technician must prove the owmeter.
Run the calibration fueling at the same ow rate of a
typical fueling.
Keep Flow Rates Even
CALIBRATION SETUP - SETUP
Packing the Hose
If you are proving the owmeter with a hose and a nozzle, you will want to make sure the hose is packed before
beginning the proving fueling. This will ensure the same shut off point at the beginning and end of the fueling.

1. In the Calibration Setup 1 screen, move the pointer to the BEGIN CALIBRATION DELIVERY eld and press the EntEr
button—do not open the hose nozzle.
2. When the hose is packed and stabilized, move the pointer on the END CALIBRATION DELIVERY eld (in the Calibration
Fueling Screen) and press the EntEr button.
3. The Calibration Setup 1 screen will reappear, and a new calibration delivery will start at “0”.
Calibration #: 1
Calibration Code:
Calibration Name:
Calibration Type:
Linearization Mode:
Gallons
AV1
Jet A1
Aviation
Setup
CALIBRATION SETUP 1
100.044
Prover Quantity
Prover Quantity list box
with volumetric prover measurement
Calibration Fueling Screen


1. With the selector switch in the calibration position,
navigate to the Calibration Setup 1 screen.
2. Move the pointer to Calibration #: and select a
number. This should be Calibration #1 for FlightConnect.
3. Move the pointer to Linearization Mode: and
select Setup.
4. Move the pointer to Pulses/Unit: and enter a
k-Factor that approximates the size of the owmeter
being calibrated. See table on page 26.
5. Move the pointer to the BEGIN CALIBRATION
DELIVERY eld.
6. Press the EntEr button to begin the calibration fueling
into a volumetric prover. A fueling screen will appear that
shows the gross volume and ow rate.
7. When the calibration run is complete, move the pointer
to END CALIBRATION DELIVERY, at the bottom of the
calibration fueling screen, and press EntEr to end the
fueling.
8. Move the pointer to Prover Quantity: and enter
the quantity indicated by the volumetric prover. The LCR
600 will automatically adjust the value in the Pulses/
Unit <k-Factor> eld to the correct value.
9. Repeat step 5 through 8. Check the prover volume and
the LCR 600 volume. If they are not within tolerance
limits, reprove the owmeter until the meter system is
within the tolerance.
Proving can only be done in gross volume.