Setup Owner manual

50
Screen 13a: Factory Setup (1/2)
Factory Setup
The Factory Setup screens are not accessible unless the
Factory Key access is entered from Screen 12 on page
49. This access code may be obtained from the Liquid
Controls service department.
Serial ID represents serial ID of the LectroCount.
User Key allows user to set the User Key used to unlock
the LectroCount from Screen 12 on page 49.
LCR Reset is used to rebuild or clear all of the elds in
the LectroCount.
Press Next (F1) to advance to Screen 13b shown
below.
Screen 13b: Factory Setup (2/2)
R100.0 is the Raw ADC value reading when a 100.0
resistor was connected to the temperature probe during
calibration.
R128.6 is the Raw ADC value reading when a 128.6
resistor was connected to the temperature probe during
calibration.
Raw ADC is the current raw ADC value.
RTD Slope is the slope used to calculate the raw
temperature value from the raw ADC value.
RTD Offset is the offset used to calculate the raw
temperature value from the raw ADC.
Press Main (F5) to return to Screen 2 on page 20. Move
pointer to Save Conguration and press ENTER to
advance to Screen 14 on page 51.
(1/2) 1
Rebuild
FACTORY SETUP
Serial ID:
User Key:
LCR Reset:
Next Cnfg Main
(2/2) 1FACTORY SETUP
R100.0:
R128.6:
Raw ADC:
RTD Slope:
RTD Offset:
Prev Cnfg Main