FINAL SETTING OF THE LIMIT CHAIN CAMS
If the gate stops short of being fully open or closed or if it bangs
against the end stops, turn off the main power and move the
appropriate limit chain cam. Each whole link on the chain
represents about 1" of gate travel. The cams should only have to
be moved one or two whole links in either direction to fine tune
the gate's limits of travel. When final adjustment has been
completed, insure that the cam nuts are properly tightened.
Review Figurez19 & 20.
FINAL SETTING OF THE OPERATOR
SENSITIVITY
The obstruction detection sensitivity was preset before turning on the
main power to prevent the operator from "self-tripping" during testing.
To set the OPEN sensitivity, start the gate in motion in the Open
direction and turn the overload potentiometer counterclockwise until
the gate stops and reverses. Then back the potentiometer off 10
degrees in the clockwise direction. Review Figure 21, Page 17.
Repeat for the Close sensitivity.
CAUTION: During this process the alarm will sound if the overload
sensor is activated two sequential times before the gate reaches a limit
(open or close). To reset the alarm sensor use constant pressure on a
control button connected to the OPEN or CLOSE input and move the
gate to a fully open or closed position or turn off and restore the power
to the operator.
Restart the gate and give the leading edge a firm blow with the heal of
your palm. Don't stand directly in the gate's path while testing the
obstruction sensitivity. The obstruction detection should respond
immediately to the blow. The overload potentiometer must be adjusted
to the most sensitive setting possible without causing "self-tripping"
due to the gate's inherent friction or to variations in the track. Try
readjusting the potentiometer several times by small increments, testing
the gate in both directions of travel, until you are satisfied.
SMARTâ„¢ Self adjusting MAximum Run Timer
The RSX1000 has a Self adjusting MAximum Run Timer, SMARTâ„¢.
The amount of time for the first few cycles of operation are registered
and averaged within the motor controller circuitry. After the first few
initial cycles, if the gate is activated and no other command is given or
an end limit (open or close) is not reached in the previously counted
cycle time plus approximately 2 seconds, the operator will be turned
off.
The RSX1000 has a thermal cutoff switch to protect the motor and
capacitor from sustaining damage. If the gate has been operated for an
excessive number of consecutive cycles the thermal cutoff switch will
open and the power will be turned off to the motor and control
circuitry. After a cooling off period the thermal cutoff switch will
automatically reset and the gate can be operated once again.
FINAL SETTING OF THE CLOSE TIMER
To alter the amount of time that the Close Timer will hold the gate
open, adjust the timer potentiometer located on the control board. See
Figure 22, page 17.
The Close Timer is adjustable from 2 to approximately 60 seconds.
Turning the potentiometer clockwise increases the delay; turning it
counterclockwise decreases the delay.
RISK OF ENTRAPMENT.
THE SENSITIVITY ADJUSTMENT MUST BE SET
MORE PRECISELY PRIOR TO COMPLETING
THE OPERATOR INSTALLATION
WARNING!