overall foil shield type cable (not included). You must use this type of cable to ensure signal integrity. After you
have made your connection it is also vital to terminate the drain wire of the cable. The drain wire is a bare wire
that runs the entire length of the cable inside the shield and along side the other four conductors. This drain wire is
to be terminated at the Earth Ground terminal of the Hub Connection Board only. Do not terminate the drain
wire at the Front End Reader.
From Hub Plus To Front End Reader
q Step 3: Making the connections for the REX and Door Contact.
The manual for the IEI Secured Series Hub Plus Controller has a very good explanation of the functions
of the REX (Request to Exit) and Door Contact input loops. Therefore in this manual we will merely
discuss the connections and the new testing feature. Wire your normally-open device to the REX
terminals and a normally-closed magnetic door contact to the DOOR INPUT terminals. A jumper cap J3
has been provided so that if you do not choose to incorporate a normally-closed door contact in your
application you can shunt the loop by placing the jumper cap on both pins. If you are including a door
contact do not forget to place J3 on one pin only otherwise the loop will be shunted and the local alarm
functions as well as auto-relock will not function.
To normally open
Exit Device
From Hub Plus Controller To normally closed
Door Contact
q Step 4: Wiring the On-Board RJ11 Jack in the Hub Connection Board (for use with
optional PC Software, available in MS-DOS and Win95 versions).
The On-Board RJ11 Jack makes connection to a PC or a Modem easier providing that the PC or Modem is located
within 25 feet of the Hub Plus Kit.
Ø If your PC or Modem is located at a distance greater than 25 feet you must use the surface mount RJ11
Jack that is included with your PC Software Kit.
If you wish to use the On-Board RJ11 Jack disconnect the white 3 conductor wire harness from Port A on the Hub
Connection Board and connect it to Port A (AUX) on the Hub Connection Board. The On-Board RJ11 Jack is
Jumper Selectable. There are 2 pin-rails located behind the modular connector on the Hub Connection Board.
Each of these pin rails has a jumper cap. If you are connecting to a PC within 25 Ft of this unit both of the jumper
caps must be on pins 2 + 3. If you are connecting to a modem within 25 Ft of this unit both of the jumper caps must
be on pin 1 + 2.