CAUTION:
A) The exhaust tubing must run outside the house, NOT INTO THE
ATTIC.
B) DO NOT exceed 30 ft. of exhaust tubing, in order to avoid motor failure
resulting from excessive back pressure.
C) DO NOT turn the exhaust piping, run within 18" of the power unit.
NOTE: After a proper location has been chosen for the power unit refer to
Figure 2 for securing the unit mounting bracket to the wall studs.
Steel tubing is also available and may be required by local building
codes.
7 of 17
Figure 3 Figure 4
120VAC 240VAC
NEMA 5-15R NEMA 6-15R
3.0 POWER UNIT ELECTRICAL REQUIREMENTS
The electrical requirements for the power units and maximum tubing
from power unit to farthest valve are as follows:
Model
Number
Voltage
(Vac)
Current
(Amps)
Circuit
Breaker
Receptacle
See Fig Type
Maximum
Tubing
AV2500 120 11 15A 3 150
AV3500 120 12 20A 3 200
AV4500 120 13 20A 3 350
AV5500 240 7 20A 4 500
FX2000 120 11 15A 3 150
FX3000 120 12 20A 3 200
FX900 240 13 20A 4 500
ZX5800 120 11 15A 3 150
ZX6000 120 12 20A 3 200
ZX7000 120 13 20A 3 350
ZX8000 240 7 20A 4 500
CAUTION: All circuit breakers must be SEPARATE and DEDICATED
as with any other major appliance. The electrical outlets
MUST match the plug WITHOUT THE USE OF ADAPTERS.