Owner's Manual
PROGRAMMING OPTIONS CHART
If the pre-programmed default values must be changed
or additional functions are desired, the following options may be programmed.
1. Enter programming mode Press 99 # (master code)
*
2.Auto entry on (no * required) Press 30 # 2 # 1 # * *
3.Auto entry off ( * required) Press 30 # 2 # 0 # * *
4.Sounder feedback on keypress Press 30 # 0 # 1 # * *
5. Sounder feedback on keypress off Press 30 # 0 # 0 # * *
6.LED options
Green LED activates when line is pulled low Press 31 # 4 # 0 # * *
Green LED activates when line is pulled high Press 31 # 4 # 1 # * *
Red LED activates when line is pulled low Press 31 # 2 # 0 # * *
Red LED activates when line is pulled high Press 31 # 2 # 1 # * *
Green LED enable Press 31 # 3 # 1 # * *
Green LED disabled Press 31 # 3 # 0 # * *
Red LED enable Press 31 # 1 # 1 # * *
Red LED disabled Press 31 # 1 # 0 # * *
Yellow LED feedback on keypress enabled Press 31 # 0 # 1 # * *
Yellow LED feedback on keypress disabled Press 31 # 0 # 0 # * *
7. Erase keypad memory and reset defaults Press 46 # 00000 # 00000 # * *
8. Change master code Press 1 # code * code *
9. Select Wiegand Format (from table below) Press 63 # 0 # format # * *
10.Set Site Number Press 64 # 0 # (site number) # * *
11.Set Group ID Press 65 # 0 # (group id number) # * *
12.Exit Program Mode Press
*
The Wiegand format, group ID, and site number is specified by the host access control system and should be deter-
mined prior to programming your DoorwGard Wiegand keypad.
There are 8 different wiegand formats supported by the DoorwGard Wiegand Series keypads. The wiegand format is
set through command 63 and must be selected prior to programming the Site Number or Group ID. The user can set up
the Site Number through command 64. The exact range for a valid Site Number is determined by the Wiegand format
which is why it must be selected first.
Some of the Wiegand formats have a Group ID embedded in their frames. Command 65 is used to set up the Group
IDs. As with the Site Numbers, the valid ranges for Group ID entries are based on the Wiegand format. If the yellow led
glows steady after entering this command, there are two possible problems. Either the current format does not support
Group IDs or the ID entered is invalid. A table showing the valid ranges for Site Numbers and Group IDs based on the
various formats is presented below.
3
Format Table
Format Frame Size PINs Sites Groups
1 26 bits 65536 256 N/A
2 28 bits 32768 256 N/A
3 29 bits 524288 256 N/A
4 30 bits 65536 256 16
5 31 bits 65536 256 32
6 32 bits 65536 2048 64
7 36 bits 1048576 256 N/A
8 29 bits 524288 256 N/A
6057130 REV 1.1