Owner's Manual
Forced Door Relay
Forced
Door
Relay
This output is utilized to inform personnel that the door had been opened without authorization.
To accomplish this, the Xtreme™ programming controller comes equipped with a relay and an inter-
nal timer circuit that is designated for this purpose. The form C relays are rated to handle one (1)
amp of current at either 12 volts or 24 volts, type AC or DC, and can turn on or off one leg of power
to a warning device. Warning device not included with IEI equipment.
To incorporate this feature into your system, simply locate one of the five connectors, each one
with three (3) wires, green, blue, and gray, located in the box with the Xtreme™ programming con-
troller. With the controller powered down, unlatch the keypad from the plastic housing and slide the
printed circuit board out of housing, exposing the connectors as shown in Diagram A.
Wiring the Forced Door Relay
1. Connect the three conductor harness with the green, blue,
and gray wire to the forced door relay jack as shown in dia-
gram A.
2. Connect green wire to V+ on siren.
3. Connect blue wire to V+ from power supply.
4. Connect V- from power supply to V- on sounder.
5. Gray wire is not used.
Xtreme™ CONTROL RELAY BOARD
DIAGRAM A.
To
Power Supply
V+
V+
V-
GRAY (NC) NOT USED
GREEN (NO)
BLUE (C)
Programming the Forced Door Relay
To program the time that the forced door output
will stay energized, program as follows:
**No programming is done at the Xtreme™ keypad.**
1. Enter programming mode. Press 99 # (master
code) *
2. Verify programmer is in programming mode.
Yellow light should be flashing slowly.
3. Press 45 # (time) # 0 # * *, time represents how
long the relay stays energized, 10 to 900 sec-
onds, in Ten second intervals, or you may
press 00 for a latched output,
requiring a valid code to reset output. Forced
door time must be programmed in intervals of
10 seconds, ie. 10, 30, 60,... up to 900 seconds.
4. Press * to exit program mode, yellow light
should not be flashing.
white wire
with orange
stripe
white wire
NOTE:This feature requires that you utilize the
normally closed door contact (input) per dia-
gram B.
DIAGRAM B.
Normally
closed
door contact