Fault Responses Output Current
COMMAND NAME CMD CODE DESCRIPTION TYPE PAGED
DATA
FORMAT UNITS NVM
DEFAULT
VALUE
IOUT_OC_FAULT_RESPONSE 0x47 Action to be taken by the device when an
output overcurrent fault is detected.
R/W Byte Y Reg Y 0x00
IOUT_OC_FAULT_RESPONSE
The IOUT_OC_FAULT_RESPONSE command instructs the device on what action to take in response to an output
overcurrent fault. The data byte is in the format given in Table 7.
The device also:
• Sets the IOUT_OC bit in the STATUS_BYTE
• Sets the IOUT bit in the STATUS_WORD
• Sets the IOUT Overcurrent Fault bit in the STATUS_IOUT command, and
• Notifies the host by asserting ALERT pin
This command has one data byte.
Table 7. IOUT_OC_FAULT_RESPONSE Data Byte Contents
BITS DESCRIPTION VALUE MEANING
7:6 Response
For all values of bits [7:6], the LTC3880:
• Sets the corresponding fault bit in the status commands and
• Notifies the host by asserting ALERT pin
The fault bit, once set, is cleared only when one or more of the
following events occurs:
• The device receives a CLEAR_FAULTS command
• The output is commanded through the RUNn pin, the
OPERATION command, or the combined action of the RUNn pin
and OPERATION command, to turn off and then to turn back on,
or
• Bias power is removed and reapplied to the LTC3880.
00 The LTC3880 continues to operate indefinitely while maintaining
the output current at the value set by IOUT_OC_FAULT_LIMIT
without regard to the output voltage (known as constant-
current or brick-wall limiting).
01 Not supported.
10 The LTC3880 continues to operate, maintaining the output
current at the value set by IOUT_OC_FAULT_LIMIT without
regard to the output voltage, for the delay time set by bits [2:0].
If the device is still operating in current limit at the end of the
delay time, the device responds as programmed by the Retry
Setting in bits [5:3].
11 The LTC3880 shuts down immediately and responds as
programmed by the Retry Setting in bits [5:3].
5:3 Retry Setting 000-110 The unit does not attempt to restart. The output remains
disabled until the fault is cleared by cycling the RUNn pin or
removing bias power.
111 The device attempts to restart continuously, without limitation,
until it is commanded OFF (by the RUNn pin or OPERATION
command or both), bias power is removed, or another fault
condition causes the unit to shut down. Note: The retry interval
is set by the MFR_RETRY_DELAY command.
2:0 Delay Time XXX The number of delay time units in 16ms increments. This
delay time is used to determine the amount of time a unit is
to continue operating after a fault is detected before shutting
down. Only valid for deglitched off state.
PMBus
COMMAND DETAILS