Datasheet

LTC3880/LTC3880-1
77
3880fc
For more information www.linear.com/LTC3880
PMBus
COMMAND DETAILS
This command has two data bytes and is formatted in Linear_5s_11s format. The part starts the calculation with a
value of –273.15 so the default adjustment value is zero.
External Temperature Limits
COMMAND NAME CMD CODE DESCRIPTION TYPE PAGED
DATA
FORMAT UNITS NVM
DEFAULT
VALUE
OT_FAULT_LIMIT 0x4F External overtemperature fault limit. R/W Word Y L11 C Y 100.0
0xEB20
OT_WARN_LIMIT 0x51 External overtemperature warning limit. R/W Word Y L11 C Y 85.0
0xEAA8
UT_FAULT_LIMIT 0x53 External undertemperature fault limit. R/W Word Y L11 C Y –40.0
0xE580
OT_FAULT_LIMIT
The OT_FAULT_LIMIT command sets the value of the external sense temperature, in degrees Celsius, which causes an
overtemperature fault. The READ_TEMPERATURE_1 value will be used to determine if this limit has been exceeded.
This condition is detected by the ADC so the response time may be up to 100ms.
This command has two data bytes and is formatted in Linear_5s_11s format.
OT_WARN_LIMIT
The OT_WARN_LIMIT command sets the value of the external sense temperature, in degrees Celsius, which causes an
overtemperature warning. The READ_TEMPERATURE_1 value will be used to determine if this limit has been exceeded.
In response to the OT_WARN_LIMIT being exceeded, the device:
• Sets the TEMPERATURE bit in the STATUS_BYTE
• Sets the Overtemperature Warning bit in the STATUS_TEMPERATURE command, and
• Notifies the host by asserting ALERT pin.
This condition is detected by the ADC so the response time may be up to 100ms.
This command has two data bytes and is formatted in Linear_5s_11s format.
UT_FAULT_LIMIT
The UT_FAULT_LIMIT command sets the value of the external sense temperature, in degrees Celsius, which causes
an undertemperature fault. The READ_TEMPERATURE_1 value will be used to determine if this limit has been
exceeded.
Note: If the temp sensors are not installed, the UT_F
AUL
T_LIMIT can be set to –275°C and UT_FAULT_LIMIT response
set to ignore to avoid ALERT being asserted.
This condition is detected by the ADC so the response time may be up to 100ms.
Values of greater than 0.1V/ms and less than or equal to 1V/ms are recommended. If a transition rate out of this range
is desired, contact the factory for more information.
This command has two data bytes and is formatted in Linear_5s_11s format.